Accessories; Product Service Life; Dimensions; Functional Description M1/100/120 F - Helios MiniVent M1/100 F Notice De Montage Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation and Operating Instructions
EN
CHAPTER 4
FUNCTION
MiniVent M1/100/120 F
3 .2

Accessories

WES 100 Wall mounting kit
WES 120 Wall mounting kit
MF 100
Mounting flange
TWH 100 Telescopic wall sleeve
TWH 120 Telescopic wall sleeve
MBR
Mounting plate
3 .3

Product service life

This unit is designed for a service life of at least 40,000 h, at S1 operation with maximum power in the
maximum permissible ambient temperature.
3 .4

Dimensions

M1/100 F
Fig .1
All dimensions in mm
4 .0

Functional description M1/100/120 F

With integrated, electronic, humidity curve-dependent automatic control unit. If 70 % relative humidity (factory setting),
is exceeded or a rapid increase in humidity, the fan will be automatically activated. At the low stage as standard. On
the relative humidity falls below 60 % (factory setting), the fan will deactivate again. Regardless of the humidity control
system, the fan can be activated with an external switch (possibly connected to light) with approx. 45 sec. start-up
delay and approx. 6-minute overrun time (function input). Manual control (On/Off) via a switch is also possible in parallel,
which is secondary to the function input.
Configuration options / factory settings*:
– Start-up delay: 0 or 45 sec*.
– Overrun time: 6*, 12, 18, 24 min.
– A button (button impulse min. 0.5 sec.) can also be connected instead of the start-up delay, which activates the fan
for the set overrun time when pressed.
A button (button impulse min. 0.5 sec.) can also be connected instead of a start-up delay and overrun time to tem-
porarily (1 hr.) deactivate the automatic humidity system.
Ref . no . 0717
Ref . no . 0486
Ref . no . 6188
Ref . no . 6352
Ref . no . 6353
Ref . no . 0281
M1/120 F
Fig .2
All dimensions in mm
4

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Minivent m1/120 f