Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Liens rapides

Helios Ventilatoren
MONTAGE- UND BETRIEBSVORSCHRIFT
INSTALLATION AND OPERATING INSTRUCTIONS
NOTICE DE MONTAGE ET D'UTILISATION
EC-Rohrventilatoren
EC In-line Fans
Ventilateurs EC pour gaines circulaires
MultiVent
®
MV EC
DE
EN
FR

Publicité

Table des Matières
loading

Sommaire des Matières pour Helios MultiVent MV EC125

  • Page 1 Helios Ventilatoren MONTAGE- UND BETRIEBSVORSCHRIFT INSTALLATION AND OPERATING INSTRUCTIONS NOTICE DE MONTAGE ET D’UTILISATION EC-Rohrventilatoren EC In-line Fans Ventilateurs EC pour gaines circulaires MultiVent ® MV EC...
  • Page 2: Table Des Matières

    DEUTSCH Inhaltsverzeichnis KAPITEL 1 SICHERHEIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Seite 1 1.0 Wichtige Informationen .
  • Page 3: Wichtige Informationen

    Montage- und Betriebsvorschrift ® MultiVent MV EC 1 .0 Wichtige Informationen KAPITEL 1 Zur Sicherstellung einer einwandfreien Funktion und zur eigenen Sicherheit sind alle nachstehenden Vorschriften genau durchzulesen und zu beachten. SICHERHEIT Dieses Dokument ist Teil des Produktes und als solches zugänglich und dauerhaft aufzubewahren um einen sicheren Betrieb des Ventilators zu gewährleisten.
  • Page 4: Einsatzbereich

    Stillstandzeiten, starke Verschmutzung, übermäßige Beanspruchung durch klimatische, technische oder elekt- ronische Einflüsse geeignet. Gleiches gilt für die mobile Verwendung der Ventilatoren (Fahr-, Flugzeuge, Schiffe, usw.). Ein Einsatz unter diesen Bedingungen ist nur mit Einsatzfreigabe seitens Helios möglich, da die Serienausführung hier- für nicht geeignet ist.
  • Page 5: Transport

    Die Geräuschangaben beziehen sich ebenfalls auf die vor stehend beschriebene Anordnung. Gehäuse vibra tionen, ungünstige Betriebsbedingungen u.a. können zu einer Erhöhung der angegebenen Werte führen. Geräuschprobleme können durch die Verwendung von flexiblen Telefonie-Schalldämpfern beseitigt werden (siehe Helios Zubehör). 2 .6 Geräuschangaben...
  • Page 6: Technische Daten

    Reicht der Strom einer EC-Versorgung nicht aus, kann eine bauseits zu stellende ausreichende externe 10 V DC eingesetzt werden (vom Netz galvanisch getrennt). Alternativ kann für vielfältige Steuerungsaufgaben das Modul „EUR EC“ von Helios eingesetzt werden. Die Steuerleitung muss das gleiche Isolationsniveau wie die Netzleitung haben 2 .10 Kondenswasserbildung...
  • Page 7: Typenschild

    Art.-Nr., SNR (Seriennummer) und PC (Produktionscode) Nummer identifizieren den Ventilator eindeutig. 3 .3 Zubehör Der Gebrauch von Zubehörteilen, die nicht von Helios empfohlen oder angeboten werden, ist nicht statthaft. Eventuell auftretende Schäden unterliegen nicht der Gewährleistung. Weiteres Zubehör s. Katalog oder www.heliosselect.de. FM . . .
  • Page 8: Lieferumfang/Konstruktiver Aufbau

    Montage- und Betriebsvorschrift ® MultiVent MV EC Alle nachfolgenden Informationen und Anweisungen sind nur für eine autorisierte Elektrofachkraft bestimmt! KAPITEL 5 5 .0 Lieferumfang/Konstruktiver Aufbau Die Ventilatoren werden serienmäßig als komplette Einheit, d.h. anschlussfertig geliefert. Sie können in beliebiger Achslage eingebaut werden – waagerecht, – senkrecht, – schräg (s. Abb. 11). INSTALLATION Bestehend aus einem Kunststoffgehäuse mit integrieten Spannbügeln, Motor und Laufrad.
  • Page 9 Montage- und Betriebsvorschrift ® MultiVent MV EC Spannbügel entfernen und Ventilatoreinheit aus der Montagekonsole entnehmen (s. Abb. 14). Abb .14 Montageposition und Bohrlöcher kennzeichnen und mit Dübeln und Schrauben (im Lieferumfang) befestigen (s. Abb. 15). Anschließend die Ventilatoreinheit wieder einsetzen und die Spannbügel montieren. Einbau Variable Positionierung des Ventilators bzw.
  • Page 10: Elektrischer Anschluss / Inbetriebnahme

    Widerständen, Winddruck u .a .m . abhängig ist, eingehalten werden . Der Einsatz von Fremdfabrikaten kann, vor allem bei elektronischen Geräten, zu Funktionsproblemen, WARNUNG Zerstörung des Reglers und/oder des Ventilators führen . Bei Einsatz seitens Helios nicht freigegebener Regelgeräte, entfallen Garantie- und Haftungsansprüche .
  • Page 11: Leistungsregelung

    Montage- und Betriebsvorschrift ® MultiVent MV EC 6 .1 Leistungsregelung – Leistungsregelung mit Drehzahl-Potentiometer PU/A Zur stufenlosen und direkten Steuerung bzw. Sollwertvorgabe von EC-Ventilatoren mit Potentiometer-Eingang. Zu-sätzlich ausgerüstet mit einem Freigabeschalter und LED-Anzeige für den Betriebszustand (abhängig der Aus- stattung der Ventilatortype). Das Potentiometer wird direkt an den Potentiometer-Eingang der Ventilatorsteuerung angeschlossen.
  • Page 12: Schaltplanübersicht

    Montage- und Betriebsvorschrift ® MultiVent MV EC 6 .2 Schaltplanübersicht Die zugeordneten Standard Anschlusspläne sind zu beachten sowie die Anschlusspläne mit Drehzahlpotentiometer PU /A 10 und Universal-Regelsystem EUR EC. 6 .2 .1 Standard Anschusspläne mit PU/A 10 SS-1194 Abb .19 MV EC 125 MV EC 160 MV EC 200...
  • Page 13 Montage- und Betriebsvorschrift ® MultiVent MV EC SS-1195 Abb .20 MV EC 250 MV EC 315 Wechselstrom, 1~, 230 V, 50 Hz mit PU/A 10...
  • Page 14 Montage- und Betriebsvorschrift ® MultiVent MV EC 6 .2 .2 Anschlusspläne mit EUR EC SS-1292 Abb .21 MV EC 125 MV EC 160 MV EC 200 Wechselstrom, 1~, 230 V, 50 Hz mit EUR EC...
  • Page 15 Montage- und Betriebsvorschrift ® MultiVent MV EC SS-1293 Abb .20 MV EC 250 MV EC 315 Wechselstrom, 1~, 230 V, 50 Hz mit EUR EC...
  • Page 16 Montage- und Betriebsvorschrift ® MultiVent MV EC 6 .2 .3 Anschlusspläne mit SU/A-3 10 (+WSUP für optionale Nachtabsenkung) SS-1229 Abb .21 MV EC 125 MV EC 160 MV EC 200 Wechselstrom, 1~, 230 V, 50 Hz mit SU/A-3 10...
  • Page 17 Montage- und Betriebsvorschrift ® MultiVent MV EC SS-1232 Abb .20 MV EC 250 MV EC 315 Wechselstrom, 1~, 230 V, 50 Hz mit SU/A-3 10...
  • Page 18 Montage- und Betriebsvorschrift ® MultiVent MV EC 6 .2 .4 Anschlusspläne mit ETR/EDR SS-1230 Abb .21 MV EC 125 MV EC 160 MV EC 200 Wechselstrom, 1~, 230 V, 50 Hz mit ETR/EDR...
  • Page 19 Montage- und Betriebsvorschrift ® MultiVent MV EC SS-1233 Abb .20 MV EC 250 MV EC 315 Wechselstrom, 1~, 230 V, 50 Hz mit ETR/EDR...
  • Page 20: 6 .3 Technische Daten Der Steuereingänge

    Montage- und Betriebsvorschrift ® MultiVent MV EC 6 .3 Technische Daten der Steuereingänge Anzahl möglicher Ventilatoren mit PU / A PU / A SU / A-3 10 EUR EC ETR / DER ETR / DER Type Poti-Versorgung Steuer / Sollwer- aus der 10 V aus der 10 V aus der 10 V...
  • Page 21 Montage- und Betriebsvorschrift ® MultiVent MV EC...
  • Page 22 ENGLISH Table of Contents CHAPTER 1 SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 1 1.0 Important information .
  • Page 23: Important Information

    Installation and Operating Instructions ® MultiVent MV EC 1 .0 Important information CHAPTER 1 In order to ensure complete and effective operation and for your own safety, all of the following instructions should be read carefully and observed. SAFETY This document should be regarded as part of the product and as such should be kept accessible and durable. The operator is responsible for observing all plant-related safety regulations.
  • Page 24: Area Of Application

    GENERAL INFORMATION to liability claims against Helios. The use of accessory parts, which are not recommended or offered by Helios, is not permitted. Any possible damages are not covered by the warranty. Changes and modifications to the unit are not per- mitted and lead to a loss of conformity, and any warranty and liability shall be excluded in this case.
  • Page 25: Shipping

    – Acoustics The noise data also refers to the above mentioned configuration. Adverse operating conditions etc. can lead to an increase of the given data. Noise problems can be eliminated by using flexible sound attenuators (see Helios accesso- ries). 2 .6...
  • Page 26: Overview

    If the power of the EC-supply is not sufficient a customer-supplied sufficient external 10 V DC can be used (gal- vanically separated from the mains). Alternatively the Helios module “EUR EC“ can be used for various control duties. The control cable must have the same insulation level as the mains cable.
  • Page 27: Type Plate

    3 .3 Accessories The use of accessory parts, which are not recommended or offered by Helios, is not permitted. Any possible dama- ges are not covered by the warranty. Other accessories see catalogue or www.heliosselect.de. FM . . .
  • Page 28: Scope Of Delivery/Design

    Installation and Operating Instructions ® MultiVent MV EC All of the following information and instructions are only intended for an authorised qualified electrician! CHAPTER 5 5 .0 Scope of delivery/Design The fans are delivered as complete units as standard, i.e. ready to install. Installation is possible in every axle position –...
  • Page 29 Installation and Operating Instructions ® MultiVent MV EC Remove clamp and fan unit from the mounting bracket (see Fig. 14). Fig .14 Mark mounting position and drill holes and fasten with dowels and screws (in scope of delivery) (see Fig. 15). Then replace the fan unit and mount the clamp.
  • Page 30: Electrical Connection / Commissioning

    ., must be observed . The use of other brands, especially other electronic devices, can lead to malfunctioning and even destruction WARNING of controller and/or fan . Controllers which have not been cleared by Helios are not liable for warranty and guarantee claims .
  • Page 31: Speed Control

    Installation and Operating Instructions ® MultiVent MV EC 6 .1 Speed control – Speed control with speed potentiometer PU/A For variable and direct control or nominal value preset of EC fans with potentiometer input. Additionally equipped with an enabling switch and LED-display for the operating status (dependant on feature of fan type). The potentiometer is attached directly to the potentiometer input of the fan control system.
  • Page 32: Wiring Diagram Overview

    Installation and Operating Instructions ® MultiVent MV EC 6 .2 Wiring diagram overview The allocated standard wiring diagrams must be observed as well as the wiring diagrams with speed potentiometer PU /A 10 and universal control system EUR EC. 6 .2 .1 Standard wiring diagrams with PU/A 10 SS-1194 Fig .19 MV EC 125...
  • Page 33 Installation and Operating Instructions ® MultiVent MV EC SS-1195 Fig .20 MV EC 250 MV EC 315 Alternating current, 1~, 230 V, 50 Hz with PU/A 10...
  • Page 34 Installation and Operating Instructions ® MultiVent MV EC 6 .2 .2 Wiring diagrams with EUR EC SS-1292 Fig .21 MV EC 125 MV EC 160 MV EC 200 Alternating current, 1~, 230 V, 50 Hz with EUR EC...
  • Page 35 Installation and Operating Instructions ® MultiVent MV EC SS-1293 Fig .20 MV EC 250 MV EC 315 Alternating current, 1~, 230 V, 50 Hz with EUR EC...
  • Page 36 Installation and Operating Instructions ® MultiVent MV EC 6 .2 .3 Wiring diagrams with SU/A-3 10 (+WSUP for optional night cooling) SS-1229 Fig .21 MV EC 125 MV EC 160 MV EC 200 Alternating current, 1~, 230 V, 50 Hz with SU/A-3 10...
  • Page 37 Installation and Operating Instructions ® MultiVent MV EC SS-1232 Fig .20 MV EC 250 MV EC 315 Alternating current, 1~, 230 V, 50 Hz with SU/A-3 10...
  • Page 38 Installation and Operating Instructions ® MultiVent MV EC 6 .2 .4 Wiring diagrams with ETR/EDR SS-1230 Fig .21 MV EC 125 MV EC 160 MV EC 200 Alternating current, 1~, 230 V, 50 Hz with ETR/EDR...
  • Page 39 Installation and Operating Instructions ® MultiVent MV EC SS-1233 Fig .20 MV EC 250 MV EC 315 Alternating current, 1~, 230 V, 50 Hz with ETR/EDR...
  • Page 40: 6 .3 Technical Data For Control Inputs

    Installation and Operating Instructions ® MultiVent MV EC 6 .3 Technical data for control inputs Number of possible fans with PU / A PU / A SU / A-3 10 EUR EC ETR / DER ETR / DER Poti feed Control / setpoint from a 10 V from a 10 V...
  • Page 41 Installation and Operating Instructions ® MultiVent MV EC...
  • Page 42 FRANÇAIS Sommaire CHAPITRE 1 SÉCURITÉ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page 1 1.0 Informations importantes .
  • Page 43: Informations Importantes

    être respectés afin d’éviter tout risque de blessure et toute situation dangereuse ! 1 .2 Consignes de sécurité Pour le fonctionnement, le raccordement et l’utilisation, contacter Helios en cas de doutes. Des informations supplémentaires sont consultables dans les normes et textes de loi.
  • Page 44: Domaine D'utilisation

    à des contraintes climatiques, techniques ou électroniques. Il en est de même pour l’utilisation mobile des ventilateurs (voitures, avions, bateaux, etc.). Une utilisation dans ces conditions est soumise à l’autorisation d’Helios, étant donné que la version de série n’est pas conçue pour ce type de fonctionnement.
  • Page 45: Réglementations - Normes

    Les données acoustiques* se référent aussi aux consignes décrites ci-dessus. Le mode de montage, des conditions d’utilisation défavorables, etc. peuvent conduire à des valeurs plus élevées que celles indiquée. Les problèmes acous- tiques peuvent être réglés à l’aide de gaines acoustiques souples (voir accessoires Helios). 2 .6 Données acoustiques...
  • Page 46: Protection Moteur

    10 V DC (avec séparation galvanique du réseau). Pour une régulation par sondes de température, pres- sion, vitesse, etc., utiliser le régulateur universel Helios EUR EC. Le câble de commande doit avoir le même niveau d’isolation que le câble d’alimentation 2 .10 Formation de condensats...
  • Page 47: Plaque Signalétique

    (type PU/A 10) et des interrupteurs à trois étages (type SU/A) adéquats sont disponibles dans le catalogue FONCTIONNALITÉS d’accessoires d’Helios. Une régulation continue de la vitesse est possible avec le régulateur universel (type EUR EC). Le régulateur de température ou de pression différentielle EDR / ETR peut aussi être utilisé.
  • Page 48: Chapitre 5 Installation

    Notice de montage et d’utilisation ® MultiVent MV EC Toutes les informations et remarques suivantes sont exclusivement destinées à un électricien qualifié ! CHAPITRE 5 5 .0 Contenu de la livraison / Composition Les ventilateurs sont livrés de série en tant qu’unité complète, c’est-à-dire prêts à raccorder. Ils peuvent être installés dans n’importe quelle position : horizontalement, verticalement ou en biais (voir fig.
  • Page 49: Montage

    Notice de montage et d’utilisation ® MultiVent MV EC Retirer les étriers et enlever l’unité ventilateur du support de montage (voir fig. 14). Fig .14 Marquer la position de montage et les trous de perçage puis procéder à la fixation avec les chevilles et les vis fournies (voir fig.
  • Page 50: Raccordement Électrique / Mise En Service

    (type PU/A 10) et des interrupteurs à trois étages (type SU/A) adéquats sont disponibles dans le catalogue d’accessoires d’Helios. Une régulation continue de la vitesse est possible avec le régulateur universel (type EUR EC). Le régulateur de température ou de pression différentielle EDR / ETR peut aussi être utilisé.
  • Page 51: Réglage De La Puissance - Avec Un Potentiomètre Pu/A

    AVERTISSEMENT des problèmes de fonctionnement ou à la destruction du régulateur et/ou du ventilateur . En cas d’utilisation d’appareils de régulation non homologués par Helios, toute demande de garantie et de responsabilité sera déclinée ! 6 .1 . Réglage de la puissance –...
  • Page 52: Courant Alternatif, Monophasé, 230 V, 50 Hz Avec Pu/A

    Notice de montage et d’utilisation ® MultiVent MV EC 6 .2 Vue d’ensemble des schémas de raccordement Les schémas de raccordement standard correspondants doivent être respectés ainsi que les schémas de raccorde- ment avec potentiomètre PU/A 10 et régulateur universel EUR EC. 6 .2 .1 Schémas de raccordement standard avec PU/A 10 SS-1194 Fig .
  • Page 53 Notice de montage et d’utilisation ® MultiVent MV EC SS-1195 Fig . 20 MV EC 250 MV EC 315 Courant alternatif, Monophasé, 230 V, 50 Hz avec PU/A 10...
  • Page 54: Schémas De Raccordement Avec Eur Ec

    Notice de montage et d’utilisation ® MultiVent MV EC 6 .2 .2 Schémas de raccordement avec EUR EC SS-1292 Fig . 21 MV EC 125 MV EC 160 MV EC 200 Courant alternatif, Monophasé, 230 V, 50 Hz avec EUR EC...
  • Page 55 Notice de montage et d’utilisation ® MultiVent MV EC SS-1293 Fig . 20 MV EC 250 MV EC 315 Courant alternatif, Monophasé, 230 V, 50 Hz avec EUR EC...
  • Page 56 Notice de montage et d’utilisation ® MultiVent MV EC 6 .2 .3 Schémas de raccordement avec SU/A-3 10 (+WSUP pour l’abaissement nocturne en option) SS-1229 Fig . 21 MV EC 125 MV EC 160 MV EC 200 Courant alternatif, Monophasé, 230 V, 50 Hz avec SU/A-3 10...
  • Page 57 Notice de montage et d’utilisation ® MultiVent MV EC SS-1232 Fig . 20 MV EC 250 MV EC 315 Courant alternatif, Monophasé, 230 V, 50 Hz avec SU/A-3 10...
  • Page 58: Schémas De Raccordement Avec Etr/Edr

    Notice de montage et d’utilisation ® MultiVent MV EC 6 .2 .4 Schémas de raccordement avec ETR/EDR SS-1230 Fig . 21 MV EC 125 MV EC 160 MV EC 200 Courant alternatif, Monophasé, 230 V, 50 Hz avec ETR/EDR...
  • Page 59 Notice de montage et d’utilisation ® MultiVent MV EC SS-1233 Fig . 20 MV EC 250 MV EC 315 Courant alternatif, Monophasé, 230 V, 50 Hz avec ETR/EDR...
  • Page 60: Chapitre 7 Entretien Et Maintenance

    Notice de montage et d’utilisation ® MultiVent MV EC 6 .3 Données techniques des entrées de tension Nombre possible de ventilateurs avec PU / A PU / A SU / A-3 10 EUR EC ETR / DER ETR / DER Alimentation Valeurs de avec l’alimen-...
  • Page 61 Notice de montage et d’utilisation ® MultiVent MV EC...
  • Page 62 Notice de montage et d’utilisation MultiVent ® MV EC...
  • Page 63 Notice de montage et d’utilisation MultiVent ® MV EC...