6.2 Condensate pipe

Condensed water that forms during operation must be drained
off frost free. To ensure proper drainage, the heat pump must
be mounted horizontally. The condensate pipe must have a
minimum diameter of 50 mm and must be fed into a sewer in
such a way that it is safe from frost. Do not discharge the con-
densate directly into clearing tanks or cess pits. The aggressive
vapours and a condensate pipe laid in an area which is not
frost-free can destroy the evaporator.
ATTENTION!
The frost line can vary according to the climatic region. The
regulations of the countries in question must be observed.
EN-6
7

Assembly

7.1 General

The following connections need to be established on the heat
pump:
Flow and return of the heating system
Control lines to the heat pump manager
Voltage supply
Condensate drain
All panelling can be removed to allow accessing the inside of
the device.
Loosen the screws for this purpose. The panels can be removed
toward the top when slightly tilted.
Opening the cover panels

7.2 Connection on heating side

The heating system connections on the heat pump are to be
made inside the device. Refer to the device information for the
connection sizes. Route the connection hoses out of the device
in a downwards direction. An optional pipe kit is available as an
accessory, which can be used to lead the connections out to
the side. Use a spanner to firmly grip the transitions when con-
necting the heat pump.
Before connecting the heating water system to the heat pump,
the heating system must be flushed to remove any impurities,
residue from sealants, etc. Any accumulation of deposits in the
liquefier could cause the heat pump to completely break down.
Once the heat pump has been connected to the heating sys-
tem, it must be filled, de-aerated and pressure-tested.