Installation

6.1 General

The device should always be installed on a permanently smooth,
even and horizontal surface. The entire frame should be in direct
contact with the ground in order to ensure an adequate sound-
proof seal and to prevent the water-bearing components from be-
coming too cold. If this is not the case, additional insulation
measures may be necessary. Furthermore, the heat pump
should be set up so that the air outlet direction of the fan is per-
pendicular to the main wind direction to allow unrestricted de-
frosting of the evaporator. The heat pump is designed for instal-
lation on even ground. In the case of different conditions (e.g.:
installation on a platform or flat roof) or there is a greater risk of
the heat pump tipping over (due to an exposed position or high
wind exposure), additional protection against tipping over must
be provided. The responsibility for the heat pump installation lies
with the specialist system construction company. During the in-
stallation, local requirements such as building regulations, static
load of the building, and wind exposure must be accounted for.
It must be possible to carry out maintenance work without hin-
drance. This is ensured when observing the distances to solid
walls as shown in the figure.
0,4 m
0,5 m
≥ 0 m
The specified dimensions are valid for stand-alone installation
only.
ATTENTION!
Do not restrict or block the area around the air intake or outlet area.
ATTENTION!
Observe country-specific building regulations!
ATTENTION!
The physical impacts must be observed for installation close to walls. No
windows or doors should be present in the area surrounding the air outlet
of the fan.
ATTENTION!
In cases of installation close to a wall, there may be more sediment in the
air inlet and outlet areas due to the air current. The colder outside air
outlet should discharge in such a way as to not increase the heat losses
in heated neighbouring rooms.
ATTENTION!
Installation in a hollow or in an inner courtyard is not permitted because
cooled air collects at ground level and is drawn in again by the heat pump
during extended periods of operation.
EN-6

6.2 Condensate pipe

Condensed water that forms during operation must be drained
off frost free. To ensure proper drainage, the heat pump must be
mounted horizontally. The condensate pipe must have a mini-
mum diameter of 50 mm and must be fed into a sewer in such a
way that it is safe from frost. Do not discharge the condensate di-
rectly into clearing tanks or cess pits. The aggressive vapours
and a condensate pipe laid in an area which is not frost-free can
destroy the evaporator.
ATTENTION!
The frost line can vary according to the climatic region. The regulations
of the countries in question must be observed.
7

Assembly

2,0 m
7.1 General
The following connections need to be established on the heat
pump:
Flow and return of the heating system
Condensate drain
Control cable to the heat pump manager
Power supply
To access the inside of the device, all side panel assemblies can
be removed as described in Cap. 5 on pag. 5.