Battery
WARNING
 Storage batteries give off explosive hydrogen gas
during recharging. Slightest spark could ignite hydrogen
and cause explosion, resulting in death or serious injury.
• DO NOT dispose of battery in a fire. Recycle battery.
• DO NOT allow any open flame, spark, heat, or lit
cigarette during and for several minutes after charging a
battery.
WARNING
 Generator and utility voltage could cause electrical
shock or burn resulting in death or serious injury.
• Installation must be performed by a licensed
professional.
• Disconnect all sources of electricity before installing or
servicing equipment.
• Ground system before applying power.
WARNING
 Battery electrolyte fluid contains acid and is extremely
caustic. Contact with battery contents could cause severe
chemical burns.
• DO NOT open or mutilate the battery
• Wear protective goggles, rubber apron, rubber boots
and rubber gloves.
• Immediately wash electrolyte from skin with water.
• If electrolyte contacts eyes, immediately flush with
water and seek medical attention.
• Spilled electrolyte is to be washed down with an acid
neutralizing agent.
 
The installer must supply and install a rechargeable 12 volt
starting battery. The starting battery MUST conform to the
specifications shown in this chart.
Battery Specifications
Specifications
Standard
Volts
12 Volt DC
Amps (Minimum)
540 CCA (Cold
Cranking Amps)
Construction
Wet Lead Acid
Terminal Type
Top Post Type Battery
Dimensions (Maximum) BCI Size 26 or BCI Size
51
24
and start without warning resulting in death or serious injury.
Install the battery as described in Servicing the Battery in
the Maintenance section of this manual. Always make sure
that the NEGATIVE cable is connected last and that the red
POSITIVE terminal insulator is secure.
Use the supplied tie-down strap to secure the battery to the
unit. Each end of the strap should be attached to the existing
tabs in the base of the unit. 

System Control Board

NOTICE Please see separate online manual: "Operation
Instructions GC1031 GENSET Controller" (part
number 80086364)  for details on set up and operation.
The generator control panel, located inside the generator
housing, is shown below. Brief descriptions of the controls
used during installation are:
(A) Menu / Programming Navigation Buttons 
(B) Stop / Config Button 
(C) Start / Select Button 
(D) Auto / Manual Button 
(E) Alarm 
(F) Digital Display — Displays generator mode, menu options,
and alarms.
Detailed descriptions of the controls are located in
the Description of Control Keys section inside the
online "Operation Instructions GC1031 GENSET
Controller" manual (part number 80086364). 
Cold Start (Less than
30°F / -1°C)
12 Volt DC
800 CCA (Cold
Cranking Amps)
Wet Lead Acid
Top Post Type Battery
BCI Size 24
WARNING
 With the battery connected, the generator may crank
• Do not connect the negative (-) cable at the battery until
the installation is complete.