Vent Pipe Installation - Noritz NR71-SV Guide D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

7.

Vent Pipe Installation

CARBON MONOXIDE POISONING
Follow all vent system requirements in accordance with relevant local or state regulation,
or, in the absence of local or state code, in the U.S. to the National Fuel Gas Code ANSI
Be sure to do
Z233.1/NFPA 54 – latest edition, and in Canada, in accordance with NSCNGPI.
Vent Piping
• Noritz N-Vent is suggested for the vent system.
If N-Vent is not used, a UL listed category III vent
system must be used.
• Follow the vent pipe manufacturer's installation
instructions.
NR71-SV
Pipe diameter
No. of Elbows
3
2
1
NR66-SV
Pipe diameter
No. of Elbows
3
2
1
*Not including the termination.
• Make the vertical section of the exhaust vent
as short as possible.
• Maintain the same vent pipe diameter from the
heater flue to the vent termination.
Clearances
Manufacturer and
Product
Noritz N-Vent
Clearances vary by manufacturer, refer to the UL
approved clearances when using materials other
than N-Vent.
12
100mm (4")
Max. Straight Vent Length*
4.5m (15')
8.1m (27')
11.7m (39')
75mm (3")
Max. Straight Vent Length*
4.5m (15')
7.5m (25')
10.6m (35')
Enclosed Unenclosed
Hor. Vert. Hor. Vert.
250mm (10")(sides)
100mm
25mm
375mm (15")(top)
(4")
(1")
150mm (6")(bottom)
WARNING
• The first vertical run from the top of the heater
should be no longer than 0.9m (3').
• Make sure vent pipe is gas tight and will not
leak. Use silicon sealant wherever necessary.
• Do not common vent or connect more than
one appliance to this venting system.
• The total vent length including horizontal & vertical
vent runs should be no less than 0.9m (3').
• Do not store hazardous or flammable sub-
stances near the vent termination and check
that the termination is not blocked in any way.
• Steam or condensed water may come out
from the vent termination. Select the location
for the termination so as to prevent injury or
property damage.
• If snow is expected to accumulate, take care
the end of the pipe is not covered with snow or
hit by falling lumps of snow.
• Consult the vent pipe manufacturer's install-
ation instructions for chimney connections.
Appliance Adapters
When using a vent system other than N-Vent,
an appliance adapter will be required to properly
connect the vent to this appliance. Consult the
manufacturer's instructions for the proper appli-
ance adapter.
25mm
(1")
( NR71-SV Only, Indoor Installation)

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Nr66-svNr71-odNr66-od

Table des Matières