Vent Pipe Installation

Vent Piping
• Use only listed category III vent materials.
• Follow the vent pipe manufacturer's installation
instructions.
Pipe diameter
No. of Elbows
3
2
1
• Make the vertical section of the exhaust vent
as short as possible.
• Maintain the same vent pipe diameter all the
way to the end.
Clearances
Manufacturer and
Product
Noritz N-Vent
Protech FasNSeal
Protech FasNSeal W2
HeatFab SafTVent
Z-Flex Z-Vent
Flex-L StaR-34
These clearances are subject to change.
Refer to the UL listing for the proper clearances.
Horizontal Vent Termination
Elbow
Appliance
Adapter
44
102mm(4")
Max. Straight Vent Length
4.6m(15')
8.2m(27')
12m(39')
Enclosed Unenclosed
Hor. Vert. Hor. Vert.
254mm (10") (sides)
76mm
102mm
381mm (15")(top)
(4")
(3")
152mm (6")(bottom)
203mm (8") (sides)
102mm
76mm
305mm (12") (top)
(4")
(3")
102mm (4")(bottom)
152mm
102mm
76mm
(6")
(4")
(3")
51mm
152mm
152mm
(2")
(6")
(6")
102mm
25mm
203mm
(4")
(8")
(1")
203mm
102mm
25mm
(8")
(4")
(1")
Hanger
Straps
Slope
Downwards
Wall
0.9m
Thimble
(3')
Max.
(Indoor Installation Only)
• The first vertical run from the top of the heater
should be no longer than 0.9mm (3').
• Make sure vent pipe is gas tight and will not
leak. Use silicon sealant wherever necessary.
• Do not common vent or connect more than
one appliance to this venting system.
• The total vent length including horizontal & vertical
vent runs should be no less than 0.9mm (3').
• Do not place any dangerous objects at the end
of the exhaust vent.
• Steam (smoke) or water drops may come out
from the end of the exhaust pipe. Select the
location for the end of the vent so that steam is
not visible, and the vent is not wet with drip-
ping water.
• If snow is expected to accumulate, take care
the end of the pipe is not covered with snow or
hit by falling lumps of snow.
• Consult the vent pipe manufacturer's install-
ation instructions for chimney connections.
Appliance Adapters
76mm
(3")
• Use the following adapters to connect the
76mm
unit to the venting system.
(3")
76mm
Manufacturer and
(3")
51mm
Product
(2")
25mm
Protech FasNSeal
(1")
HeatFab SafTVent
25mm
(1")
Z-Flex Z-Vent
Flex-L Star-34
Termination
Part No.
FSAA4
9401RYPK
2SVWA04
SRASPSA4
• Terminate at least 305mm(12")
above grade or abovesnowline.
• Terminate at least 2.1m(7')
above a public walkway,
1.8m(6') from the combustion
air intake of any appliance, and
0.9m(3') from any other build-
ing opening, gas utility meter,
service regulator etc.
• Terminate at least 0.9m(3')
above any forced air inlet
within 3m(10'), 1.2m(4') below,
1.2m(4') horizontally from and
0.3m(1') above any door,
window, or gravity air inlet into
any building per National Fuel
Gas Code ANSI Z223.1/NFPA
54.
• Slope the horizontal vent 1/4"
downwardsforevery305mm(12").
• Use a condensation drain if
necessary.