MICROPROCESSOR-CONTROLLED LOGIC
DIAGNOSTIC LEDS
LINE INPUT PROTECTION WITH FUSE
INCORPORATED ELECTRONIC TORQUE LIMITER
ELECTRONIC PEAK LOAD CONTROL
INCORPORATED FLASHING LIGHT
CONNECTOR FOR RECEIVER BOARD
CONNECTION TO THE TERMINAL BOARD
1-2
power supply input 230 Vac 50Hz.
3-4
flashing light output 230 Vac 50W max. The signal delivered is already suitably
modulated for use as it is. The flashing frequency is slightly faster during closing.
5-6-7
230 Vac single-phase motor M1 output, 300 W max.
common = 6; opening = 5; closing = 7
connect the capacitor between terminals 5 and 7.
8-9
24Vac,10W output for powering photocells, outside receivers, etc.
11-12 24 Vac Max 3W output for powering aux relay for courtesy light. The light comes
on when the maneuver starts and goes off after about 3 minutes.
15-16 Input for closing limit switch (normally-closed contact); 15 = COMMON
Input for opening limit switch (normally-closed contact); 15 = COMMON
15-18 input for STOP button (normally-closed contact); pressing this button causes the
automation to stop.
The next command always triggers an opening cycle. 15 = COMMON
15-19 Input for pressure-sensitive edge (mechanical edge) or other safety and/or other
devices (photocells, mechanical edges, etc.) 15 = COMMON
15-20 input for OPEN/CLOSE button (normally-open contact); for its use, refer to DIP
switches 2 and 3, 15 = COMMON.
21-22 Input for aerial 21 = SIGNAL. 22 = EARTH.
23-24 output for 2
LOGIC ADJUSTMENTS TRIMMER
T.L.
adjusts operating time: from 5 to 125 seconds.
T.C.A. adjusts automatic re-closing time; from 5 to 125 seconds (see dip switch nr.1)