Grandeurs D'influence - Chauvin Arnoux C.A 6456 Notice De Fonctionnement

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

4.5.3
MEASUREMENT PROCEDURE
The measurement is started automatically and is continuous.
4.5.4
MEASUREMENT RESULTS
The measured values and complementary calculated results are described in the table of § 4.1.4
(position
of the switch).
4.5.5
CHARACTERISTICS
4.5.5.1 Measurement ranges and accuracy
Particular reference conditions :
- peak factor = 1.414,
- DC component < 0.1%,
- operating frequency domain = 15.3 to 450Hz.
Characteristics with an MN 20 current probe:
Display range
Specified measurement domain
Accuracy
Note : in measurement of I
, the accuracy is ancreassed by 5%.
SEL
Caractéristiques avec une pince C172 :
Display range
Specified measurement domain
Accuracy

4.5.5.2 Grandeurs d'influence

Influencing
quantities
Température
Relative humidity
Power supply voltage
Frequency (without the current probe)
Common mode rejection in
AC 50/60Hz en DC
www.electronicaembajadores.com
400mA
5.0 - 399.9mA
2% + 10pt
400mA
5.0 - 399.9mA
2% + 10pt
Limits of the domain of
use
-10 to+ 55 °C
1 %/10 °C ± 1pt
10 à 85 % HR at 45°C
1 % / V + 1pt
6,8 to 10 V
15.3 to 450Hz
0 to 500 V AC
76
4A
40A
0.400 - 3.999A
4.00 - 20.00A
1,5% + 2pt
1.2%+2pt
4A
40A
0.400 - 3.999A
4.00 - 20.00A
1,5% + 2pt
1,2%+2pt
Variation of the measurement
Typical
Maximum
2 %/10 °C + 2pt
2 %
3 % + 2 pt
2%/ V + 2pt
0,5%
1%
50dB
40dB

Publicité

Table des Matières
loading

Table des Matières