Chauvin Arnoux C.A 6456 Notice De Fonctionnement page 260

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

PUSH
btn
I
12 mA
∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ ∆ n
PUSH
btn
The type of compensation of the measuring cables (see § 3.3)
the alarm threshold Z
or R
L
the number of measurements to be counted to smooth the measurement (see § 3.2).
=> Set the switch to the REARTH position,
=> Activate the alarm by pressing the ALARM key,
=> Select the measuring current:
=> high (
) for a greater accuracy:
- if there is no tripping of a earth fault breaker (measurement made upstream of the RCDs),
- if the earth fault breaker concerned is short-circuited for greater accuracy,
- if the earth fault breaker concerned is short-circuited for greater accuracy
- if the earth fault breaker concerned is short-circuited for greater accuracy,
- in the case of a selective measurement using a current probe.
=> low (
) for a quick check :
=> Make the connections as indicated below, according to the type of installation to be checked.
=> Compensate the measuring cables (see § 3.3),
Case of an installation with a TT type neutral situation :
=> Connect the mains socket (or the
3 separate cables) to the installation
to be tested,
=> Plant the auxiliary rod at a distance
> 25 m from the earth electrode.
www.electronicaembajadores.com
x5
MORE
Selecteion of current
Selecteion of current
MORE
twice to exit from programming
:
L
64