Electrical Connection; Electrical Installation - Dimplex LIK 12TU Instructions D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

English

7.5 Electrical connection

7.5.1 General
All electrical connection work must be carried out by a trained
electrician or a specialist for the specified tasks in accordance
with the
installation and operating instructions,
country-specific installation regulations (e.g. VDE 0100),
technical connection conditions of the energy suppliers and
supply grid operators (e.g. TAB) and
local conditions.
To ensure that the frost protection function of the heat pump
works properly, the heat pump manager must remain connected
to the power supply and the flow must be maintained through the
heat pump at all times.
The switching contacts of the output relay are interference-sup-
pressed. Therefore, depending on the internal resistance of the
measuring instrument, a voltage can also be measured when the
contacts are open. However, this will be much lower than the line
voltage.
Extra-low voltage is connected to controller terminals N1-J1 to
N1-J11; N1-J19; N1-J20; N1-J23 to N1-J26 and terminal strip
X3; X5.1. If, due to a wiring error, the line voltage is mistakenly
connected to these terminals, the heat pump manager will be de-
stroyed

7.5.2 Electrical installation

All electrical cables fed into the device, that have to be connected
in the switch box or fixed on the switch box (on the designated
"T-cut"), must have a length and routing that enables the switch
box to be removed and put to one side (for service work) without
having to disconnect the cables again (see Cap. 3.2 on pag. 4).
1)
The electric supply cable for the output section of the heat
pump (up to 5-core) is fed from the electricity meter of the
heat pump via the utility blocking contactor (if required) into
the heat pump Connection of the mains cable to the switch
box of the heat pump via terminal X1: L1/L2/L3/N/PE.
An all-pole disconnecting device with a contact gap of at
least 3 mm (e.g. utility blocking contactor or power contac-
tor) and an all-pole circuit breaker with common tripping for
all external conductors must be installed in the power supply
for the heat pump (tripping current and characteristic in com-
pliance with the device information).
ATTENTION!
Ensure that there is a clockwise rotating field: With incorrect wiring the
starting of the heat pump is prevented. A corresponding warning is
indicated on the display of the heat pump manager (adjust wiring).
2)
The three-core electric supply cable for the heat pump man-
ager (heating controller N1) is fed into the heat pump .
Connection of the control line to the switch box of the heat
pump via terminal X2: L/N/PE.
Details on the power consumption of the heat pump are
listed on both the product information sheet and the type
plate.
The (L/N/PE~230 V, 50 Hz) supply cable for the heat pump
manager must have a constant voltage. For this reason, it
should be tapped upstream from the utility blocking contac-
tor or be connected to the household current, as important
protection functions could otherwise be lost during a utility
block.
EN-10
3)
The utility blocking contactor(K22) with 3 main contacts (1/3/
5 // 2/4/6) and an auxiliary contact (NO contact 13/14)
should be dimensioned according to the heat pump output
and must be supplied by the customer.
The NO contact of the utility blocking contactor (13/14) is
looped from terminal strip X3/G to connector terminal X3/A1.
CAUTION! Extra-low voltage!
4)
The contactor (K20) for the immersion heater (E10) of mono
energy systems (HG2) should be dimensioned according to
the radiator output and must be supplied by the customer. It
is controlled (230 V AC) by the heat pump manager via ter-
minals X2/N and X2/K20.
5)
The contactors mentioned above in points 3, 4 and 5 are in-
stalled in the electrical distribution system. Mains cables for
the installed heaters must be laid and secured in accord-
ance with the valid standards and regulations.
6)
All installed electric cables must have permanent wiring.
7)
The heat circulating pump (M13) is activated via the contact
N1-J13/NO5. The connection points for the pump are X2/
M13 and X2/N. When using pumps where the switching ca-
pacity exceeds the output, a coupling relay must be inter-
posed.
8)
The auxiliary circulating pump (M16) is activated via the con-
tact N1-J16/NO9. The connection points for the pump are
X2/M16 and X2/N. When using pumps where the switching
capacity exceeds the output, a coupling relay must be inter-
posed.
9)
The domestic hot water circulating pump (M18) is activated
via the contact N1-J13/NO6. The connection points for the
pump are X2/M18 and X2/N. When using pumps where the
switching capacity exceeds the output, a coupling relay must
be interposed.
10) The return flow sensor is integrated into the heat pumps and
is connected to the heat pump manager via the control line.
The return flow sensor must be installed in the immersion
sleeve in the manifold only when a dual differential pressure-
less manifold is used. The single-core wires are then con-
nected to terminals X3/GND and X3/ R2.1. Bridge A-R2 (sit-
uated between X3/B2 and X3/1 when delivered) must then
be moved to terminals X3/1 and X3/2.
11) The external sensor (R1) is connected to terminals X3/GND
and X3/R1.
12) The domestic hot water sensor (R3) is included with the do-
mestic hot water cylinder and is connected to terminals X3/
GND and X3/R3.
13) The electrical integration of the accessory "electric built-in
radiator" is described in the manual for the accessory.
7.5.3 Connecting an electronically
regulated circulating pump
Electronically regulated circulating pumps have high starting cur-
rents, which may shorten the service life of the heat pump man-
ager. For this reason, a coupling relay is installed or must be in-
stalled between the output of the heat pump manager and the
electronically regulated circulating pump. This is not necessary if
the permissible operating current of 2 A and a maximum starting
current of 12 A are not exceeded in the electronically regulated
circulating pump or if express approval has been issued by the
pump manufacturer.
ATTENTION!
It is not permitted to connect more than one electronically regulated
circulating pump via a relay output.
452160.66.66 · FD 9908
LIK 12TU
www.gdts.one

Publicité

Chapitres

Table des Matières
loading

Table des Matières