VIII.7. MODBUS and BACNET table
INPUT REGISTER
Function
System status
External temperature
Operating time of the blower
fan
Operating time of the recovery
fan
Supply temperature
Extraction temperature
Fresh air pressure
Recovery air pressure
Fresh air flow rate
Recovery air flow rate
CO2
Humidity
Analogue output
Analogue output
Analogue output
Analogue output
Analogue output
Description
Modbus:
0= stop
1= start
2= low speed start
3= maximum speed start
4= normal speed start
5= In operation
8= CO2 operation
9= Night cooling
11= In shutdown
BACNET:
1= stop
2= start
3= low speed start
4= maximum speed start
5= normal speed start
6= In operation
9= CO2 operation
10= Night cooling
12= In shutdown
LOBBY
®
LOBBY
®
MAC2
/QUATTRO
®
®
MAC2
/QUATTRO
®
®
DIVA
®
0-10 V heating (WATER COIL)
0-10 V Heat exchanger
0-10 V Heat exchanger
0-10 V Supply
0-10V Recovery
Exo
Modbus
Bacnet
type
address
address
X
3
MSV,40003
R
1
AV,40001
R
4
AV,40004
R
5
AV,40005
R
7
AV,40007
R
9
AV,40009
R
13
AV,40013
R
14
AV,40014
R
15
AV,40015
R
16
AV,40016
R
17
AV,40017
R
23
AV,40023
R
54
R
55
R
56
R
57
R
58
Default
value
47