ENGLISH
Description
ADP (bridge if not used)
DAD (bridge if not used)
THA / THS
(bridge if not used)
ED-TOUCH
MF LS
MF HS
ARR EST
BC
BE
Heating pump
(PREMIUM BC)
Cooling pump
(PREMIUM BC)
AL
NC (Night cooling)
(LOBBY®)
TRPS
DEPS
TRPR
DEPR
CO2
BF
DEP FS
DEP FR
RMS
RMR
WHEEL
0-10V S
0-10V R
* Connect directly to the CORRIGO controller
** Connect directly to the CORRIGO controller and at a maximum 8A to the DO group
16
Terminals
Connection
1-2
Connect to the terminals of a firefighter remote shutdown NF contact
Connect to the DAD fault contact
3-4
Connect to the NF contact of the THA (PREMIUM BC)
5-6
Connect to the NF contact of the THS (PREMIUM BE)
7-8 + A*-B* (port2)
Connect to the touch screen remote control
9-10
Connect to the external NO voltage-free Low Speed Forced Run contact
11-12
Connect to the external NO voltage-free High Speed Forced Run contact
13-14
Connect to the external NO voltage-free External Forced Shutdown contact
15-16-17
BC: Connect to the 3-way valve of the hot water coil (see section IV.12)
BE: Connect to the static contactor of the electric heater battery (see section IV.14)
18 + DO3**
Connect to the M/A of the hot water pump (Caution: max. 24 V 2 A to be connected
18 + DO3**
via relay) (see section IV.12)
Connect to the M/A of the cold water pump (Caution: max. 24 V 2 A to be
19 + DO4**
connected via relay)** (see section IV.12)
24 V output available in the event of system malfunction (Caution: max. 24 V 2 A to
20 + DO5**
be connected via relay)
24 V output available if the system is configured with the LOBBY
20 + DO7**
opening the terminal dampers during Night Cooling operation. (Caution: max. 24 V
2 A to be connected via relay)
23 / Agnd* + UI1*
Connect to the supply pressure sender (see section IV.8)
Connect to terminals 1 and 3 of the supply DEP (see section IV.7)
24 + UI1*
25 / Agnd* + UI2*
Connect to the recovery pressure sender (see section IV.8)
26 + UI2*
Connect to terminals 1 and 3 of the return DEP (see section IV.87)
27 / Agnd* UI3*
Connect to the CO2 sensor (see section IV.10)
BF: Connect to the 3-way valve of the hot water coil (see section IV.12)
28-29-30
Connect to terminals 1 and 3 of the DEP supply filter (see section IV.6)
31-32
33-34
Connect to terminals 1 and 3 of the DEP return filter (see section IV.6)
35 + DO1**
Connect to terminals 1 and 2 of the motorised supply damper
36 + DO2**
Connect to terminals 1 and 2 of the motorised recovery damper
37-38
Connect to the 0-10 V input of the wheel (see section IV.5)
21-22
Connect to the wheel malfunction return terminals (see section IV.5)
39-40
Connect to the fan or to the supply variator (see sections VIII.2 to 5)
41-42
Connect to the fan or the recovery variator (see sections VIII.2 to 5)
EC option for
®