V.8.c. BACNET

A simplified BACNET table appears at the end of these instructions.
Access: Configuration/Communication
The BACNET IP is to be activated [(7) section V.7]. Possibility to determine the DHCP address or set the fixed IP [(5)(6)
section V.7]. Possibility to define the ID parameters, the port number... [(8) section V.7].
The BACNET MSTP is to be activated [(3) section V.7]. Possibility to modify the communication speed, ID, address, etc.
[(4) section V.7]. Speed = 9600 / MAC address = 0 / Device ID = 2640 / Max master = 127
BACNET type
10XXX = Binary read and write
20XXX = Binary read
10XXX = Analogue read and write
20XXX = Analogue read
10XXX = Multistate read and write
20XXX = Multistate read
(XXX = MODBUS address)
AV = Analogue value
BV = Binary value
MSV = Multistate value
BMMD address: The BBMD address is used to locate devices connected to different BACnet/IP subnetworks and separated
by an IP router. The address is entered as he host; the host can be the host name if DNS is configured. If the DNS is not
configured, it will be necessary to enter the host address in the format xxx.xxx.xxx.xxx followed by the port number (default
setting 47808)
MAC: The MAC address of the device. This must be unique for the sub-network only.
Device ID: The ID of a device, used to identify it on the BACnet. This number must not be duplicated anywhere else on the
BACnet and therefore must be unique. To set an ID value of 34600, the low number must be set to 4600 and the high
number to 3
For more information, refer to the CORRIGO images at http://www.regin.se

V.8.d. LON communication (if CORRIGO with LON option)

Define the parameters of the LON function as follows
In the menu Configuration/Communication/Function port 2 = Activate port 2 in the extension unit. Go to the right and declare
the extension unit 1 as CORRIGO E28 LON
The key for the PIN function is located on the rear of the controller.
The communication table at http://www.regincontrols.com
V.8.e. Activation of the fire protection function
Defining the input parameters
Access: Configuration/Input Output/DI/ DI8
Declare input DI8 as "Fire protection Al" "NO"
Definition of function parameters
Access: Configuration/Fire protection function
Select the desired mode on activation of the fire protection function
"Shutdown": Total system shutdown
"Continuous operation" Startup or maintenance of unit operation in HS mode. The fire protection function will have priority
over all other alarms.
"Normal operation": System operation maintained in accordance with parameters defined on site (Shutdown/LS/HS)
"Blower fan only" Startup or maintenance of the blower fan in HS operation (recovery fan shutdown)
"Recovery fan only" Startup or maintenance of the blower fan in HS operation (blower fan shutdown).
Definition of the alarm parameters
Access: Configuration/Alarm configuration
Enter alarm number "10", go to the right and enter in priority "C alarm" "Active"