V.4.c. Modifying the temperature setpoint
[(8) section V.3.b]
Access: Temperature control
The setting is based on the temperature of:
the supply with external compensation (standard setting). In other words, the setpoint for the temperature changes
according to the external temperature. This rule is defined in order to comply with RT 2012
Recovery.
V.4.d. Forced shutdown of the control unit or forced LS or HS run via the remote control 27
[(7)section V.3.a]
Access: Operating mode/Operating mode
It is possible to stop (7) (shut down) the system via the CORRIGO command or execute a forced LS run (7) (manual speed 1/2)
or HS (7) run (manual speed 1/1). As standard, the system operates in Automatic mode controlled by the timers (7) (Auto)
An alarm will be generated the moment the system is taken out of Auto mode. Note that the manual speed 1/1 and
manual speed 1/2 modes are used exclusively for activation and repairs. Any other setting will cause a system
!
malfunction.

V.4.e. Language selection

[(10) section V.3]
Access: Initial screen/Language selection
V.5. Intermediate settings (service level)
In order to set the parameter type, the Night Cooling parameters and CO2 setpoint you need access to the configuration
menu at system level. This requires access authorization at "Function" level. The procedure is as follows.
Access rights
Enter the code 2222 using the arrow keys then press OK to confirm. Press the left arrow key twice to access the menus. If
you make a mistake, press C twice and repeat the operation.
3
Log on
Enter password 2222
Actual level: SERVICE