Vortice VORT NRG ECR Notice D'emploi Et D'entretien page 36

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

ENGLISH
Title
6
Filter obstructed
External frost
8
protection
15
High supply temp.
Heater batt.
23
overheating
Ext. temp sensor
27
error
Heat exchanger
29
rotation check
31
VAS pressure error
32
VAR pressure error
35
Manual
36
...in manual mode
to 44
48
Low charge
36
Description
Type Time
Over 30 Pa if the fan
is in in operation)
DI1 should be open
("Ouv") in the
C
absence of faults
Ext DI3 should be
closed ("Fer") in the
C
absence of faults
Ext AI1 has exceeded
A
50° C
Ext DI3 should be
closed ("Fer") in the
A
absence of faults
Check the
A
value on Al2
Check value
C
on Ext DI6
Difference of more
than 50 Pa between
the supply setpoint
C
and the temperature
reading on Ext UAI1
Difference of more
than 50 Pa between
the supply setpoint
C
and the temperature
reading on Ext UAI2
Operation in
C
manual mode
Some functions have
switched to manual
C
mode.
Internal battery error
A
Cause
5. Check the connections of the clear plastic pipes (see IV.7
and IV.8)
6. Water in clear plastic pipe
7. 0-10 V motor inverted
1. The filter/s is/are obstructed
2. The filter pressure switches are connected incorrectly
(the pressure switches must be set to 150
5 s
Pa for G4 and 200Pa for F7).
3. Check the connections of the clear plastic pipes (see
section IV.6)
1. The THA thermostat is not set to 5° C
2. The THA thermostat is out of service
120 s
3. The circulation pump is out of service
4. The 3-way valve is incorrectly wired or hydraulically
connected or out of service
1. The supply temperature has exceeded 50° C
2. The temperature setpoint is too high.
30 s
3. The supply fan has stopped (AS fan fault) while the
heater battery is working at full operating speed.
4. Supply ducts obstructed
1. The THS safety thermostat has tripped. To reset the THS,
press the reset button on the electric heater battery.
5 s
2. Power supply failure
3. The supply fan has stopped (AS fan fault) while the heater
batter is working at full operating speed.
1. The external temperature sensor SEG is out of service
5 s
2. The external temperature sensor SEG is wired incorrectly
(see section IV.3)
300 s
1. The heat exchanger belt is damaged
1. The supply network does not correspond to the selected
30 min
fan or to the pressure setpoint.
2. The filter is obstructed
1. The supply network does not correspond to the selected
30 min
fan or to the pressure setpoint.
2. The filter is obstructed
1. Fault for information only (the system has switched to
5 s
shutdown in LS or in HS directly on the display (see (7)
section V.3.a)
5 s
1. In the Manual/Auto menu all options should be set to Auto.
1. The internal battery of the CORRIGO controller is out of
5 s
service. Replace the battery quickly to avoid losing the

Publicité