V.7. Administrator settings

Activation of communication, dehumidification and the fire protection function requires access to the Configuration menu at
system level. This requires access authorization at "Admin" level. The procedure is as follows.
Access rights
Enter the code 1111 using the arrow keys then press OK to confirm. Press the left arrow key twice to access the menus. If
you make a mistake, press C twice and repeat the operation.
V.7.a. Configuration menu with Admin level access
Configuration
1 and 2 Activation of MODBUS RS485 and parameter modification (see section V.8)
3 and 4 Activation of BACNET MSTP and parameter modification (see section V.8)
5 and 6 parameter modification TCP/IP address (see section V.8)
7 and 8 Activation of BACNET IP and parameter modification (see section V.8)
9 Repeater addressing (see section V.8)
32
Log on
Communication
System
Enter password: 1111
Actual level: ADMIN
Door 1
Communication
Slave
Modbus slave
Door 1
On (1)
Comunicazione
Bacnet
MSTP
Porta 1
Attivo (3)
TCP/IP
DHCP: SÌ (5)
Current Ip :
Communication
BACNET IP
On (7)
Address
PLA: 254 (9)
ELA: 254 (9)
Address Modbus: 1 (2)
Speed: 9600 Bps (2)
2 bit stop: YES (2)
Equality: No (2)
Nome dispositivo: - (4)
Mac: 0 (4)
Id dispositivo basso: 2640 (4)
Id dispositivo alto: 0 (4)
(x10000)
Velocità: 9600 Bps(4)
Ad. master max: 127 (4)
IP: - (6)
Subnet Mask - (6)
Subnet Mask - (6)
Gateway - (6)
Device name: - (8)
Address BBMD: 0 (8)
Id low device: 2640 (8)
Id high device: 0 (8)
(x10000)
N° door UDP low: 7808(8)
N° door UDP high: 4(8)
(x10000)