Final Work - Dimplex LAW 6IMR Instructions D'installation Et D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

8.2.2 Indoor component
Two supply cables must be connected to the indoor component:
The power supply to the heat pump and the control voltage for
the integrated heat pump manager (see Appendix Chapter 3.3).
(Load: 3~; 1x 5-core; control: 1~; 1x three-core) The VDE direc-
tives and regulations and local conditions must be taken into ac-
count in the design and installation of the cables.
Only with the heat pump combination with the 6 kW or 9 kW out-
door unit can the power supply take place with two separate sup-
ply cables (2x 1~/N/PE; 230 VAC; 50 Hz) via load distribution.
Otherwise, the power supply always takes place with one cable
(3~/N/PE; 400 VAC; 50 Hz).
NOTE
The positions of the copper link cables in the terminals for the power
supply must be complied with. In factory default, the copper link cables
come connected correctly for a single supply cable. For the 9 kW unit and
when using two supply cables, the positions of the copper link cables
must be changed (see Appendix, Load connection diagram Chap. 2.3).
The supply cable for the output section of the heat pump (up to
5-core) is fed from the electricity meter of the heat pump via the
utility blocking contactor (if required) into the heat pump (see
heat pump operating instructions for supply voltage). An all-pole
disconnecting device with a contact gap of at least 3 mm (e.g.
utility company blocking contactor or power contactor) as well as
an all-pole circuit breaker with common tripping for all external
conductors must be installed in the power supply for the heat
pump (tripping current and characteristic in compliance with the
device information).
The supply cable (1~L/N/PE~230 V, 50 Hz) for the heat pump
manager must have a continuous voltage. For this reason, it
should be tapped upstream from the utility blocking contactor or
be connected to the household current, because otherwise im-
portant protection functions could be lost during a utility block.
The correct control voltage must be ensured according to the
general information leaflet/rating plate.
The utility blocking contactor (K22) with 3 main contacts (1/3/5 //
2/4/6) and an auxiliary contact (NO contact 13/14) should be di-
mensioned according to the heat pump output and must be sup-
plied by the customer. The NO contact of the utility blocking con-
tactor (13/14) is looped from terminal strip X3/G to connector
terminal N1-J5/ID3. CAUTION! Extra-low voltage!
The power supply must be connected to terminal strip X1 and the
control voltage to terminal X2 in the indoor component.
For detailed instructions on how to connect the external compo-
nents as well as how the heat pump manager functions, please
refer to the device connection diagram and the operating instruc-
tions supplied with the heat pump manager.
In factory default, the 2nd heat generator is connected with a 6
kW heat output. To reduce the output to 4 kW or 2 kW, one or
both of the two copper link cables must be removed from terminal
X7 (see circuit diagram).
For detailed information, see circuit diagrams in the Appendix.
The electrical cables can be fed into the unit from below (in the
refrigerant connection area) or from above (a duct moulded in PU
foam is located under the cylinder cover).
www.dimplex.de

8.3 Final work

Once the pipes and electric cables have been connected, the
pipes must be bent and a number of tests carried out. The leak
test must be carried out with particular care, as a refrigerant leak
results in a direct reduction in output.
Leaks are also difficult to identify once the installation is com-
plete.
8.3.1 Pipe bends
Bend the pipe by covering the connection cable and refrigerant
pipe (between the indoor and outdoor unit) with insulation and fix
the insulation in place with two adhesive tapes.
1)
Fix the refrigerant pipe, mains cable and connection cable
with adhesive tape from bottom to top. Fix the bound pipe-
work along the wall.
2)
Form a siphon to prevent water from entering the chamber
and electrical components.
3)
Fix the pipework to the wall using clamps or similar.
Wrap the pipework in adhesive tape
1)
Fix the pipes, mains cable and connection cable with adhe-
sive tape from bottom to top. If they are fixed from top to bot-
tom, rain could enter into the pipes or cables.
2)
Fix the bound pipework along the external wall with clamps
or similar.
3)
A siphon prevents water from entering the electrics.
6HDO VPDOO JDSV
RSHQLQJ DURXQG
RSHQLQJ DURXQG
DURXQG WKH SLSH
WKH SLSLQJV ZLWK
WKH SLSLQJV ZLWK
HJ ZLWK VLOLFRQ
JXP W\SH VHDOHU
JXP W\SH VHDOHU
$ VLSKRQ SUHYHQWV ZDWHU IURP HQWHULQJ WKH HOHFWULFV
452162.66.04 · FD 9606
LAW 6IMR - LAW 14ITR
3LSH
'UDLQ KRVH
$GKHVLYH WDSH
QRW XVHG
QDUURZ
:UDSSHG LQ
DGKHVLYH WDSH
ZLGH
$GKHVLYH WDSH
'UDLQ KRVH
QRW XVHG
.OHEHEDQG
.OHEHEDQG
$GKHVLYH WDSH
&RQQHFWLRQ FDEOH
5HIULJHUDQW SLSHV
0DLQV FDEOH
EN-13

Publicité

Chapitres

Table des Matières
loading

Ce manuel est également adapté pour:

Law 9imrLaw 14imrLaw 14itr

Table des Matières