Jumper Positions For Inputs - Lenze E82ZAFAC001 Instructions De Montage

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Jumper positions for inputs

1
3
2
4
)
Note!
If a setpoint potentiometer is supplied internally via X3.2/9, the jumper must
be set between 0 ... +5 V. Otherwise it is not possible to use the whole speed
range.
Analog inputs
X3.1/1U
Analog input 1, AIN1
X3.1/2U
Analog input 2, AIN2
Analog inputs
X3.1/1I
Analog input 1, AIN1
X3.1/2I
Analog input 2, AIN2
1)
open−circuit monitored
EDK82ZAFAC−001 DE/EN/FR 6.0
5
7
9
6
8
10
Jumper
Code
C0034/1 = 0
Jumper
Code
C0034/2 = 0
Jumper
Code
C0034/1 = 2
Jumper
Code
C0034/2 = 2
l
Jumper positions for inputs
Lenze setting (bold printing in tables)
Ÿ 1 − 3
Ÿ 2 − 4
Ÿ 7 − 9
Ÿ 8 − 10
Possible levels
0 ... +5 V
7 − 9: free
C0034/1 = 0
8 − 10: free
C0034/2 = 0
Possible levels
0 ... +20 mA
+4 ... +20 mA
optional
C0034/1 = 3
optional
C0034/2 = 3
Commissioning
0 ... +10 V
−10 ... +10 V
7 − 9
C0034/1 = 1
8 − 10
C0034/2 = 1
+4 ... +20 mA
optional
optional
C0034/1 = 4
optional
optional
C0034/2 = 4
5
7 − 9
8 − 10
1)
33