Preparing the controller for communication

82XX / 8200 vector frequency inverter
Step
Procedure
1.
The controller can only be enabled via PROFIBUS if the Lenze parameter
operating mode (C0001) is set to 3. This setting can be made using the
EMZ9371BC keypad or directly via PROFIBUS.
Examples for PROFIBUS Write (C0001 = 3):
– Index = 0x5FFE
(results from 0x5FFF * (C0001)
– Subindex: 0
– Value: 0d30000
2.
Terminal 28 (CINH) is always active and must be set to HIGH level during
PROFIBUS operation (see the Operating Instructions for the controller).
– Otherwise, the controller cannot be enabled by PROFIBUS
(DRIVECOM device status "OPERATION ENABLED").
– With 821X, 8200 vector and 822X, the QSP (quick stop) function is
always active. If QSP is assigned to an input terminal (Lenze setting:
not assigned), this terminal must be at HIGH level during PROFIBUS
operation (see the Operating Instructions for the controller).
3.
The controller now accepts control and parameter−setting data from the
PROFIBUS.
4.
Select the speed setpoint with a value unequal 0.
5.
Change to status "READY TO SWITCH ON .
Select value for DRIVECOM control word:
0b0000 0000 0111 1110 (0x007E).
6.
Wait until controller has changed to status "READY TO SWITCH ON".
Value for DRIVECOM status word:
0bxxxx xxxx x01x 0001.
7.
Change to status "OPERATION ENABLED".
Select value for DRIVECOM control word:
0b0000 0000 0111 1111 (0x007F)
8.
Wait for "OPERATION ENABLED"
EDKMF2133 DE/EN/FR 6.1
Preparing the controller for communication
; see Lenze code addressing
hex
l
Commissioning
see
^ 44
^ 44
^ 44
^ 44
^ 44