Troubleshooting

Below, some typical problems are shown that may arise during the installation and use of the supervisor
program, with the possible causes and solutions.
PROBLEM
It is impossible to install the WinLog - Incorrect indication of the source and/or
program
The program does not start
After the installation of a new version - The new program has been installed in
of WinLog, the program behaves like the same directory as the old program
the old version
The mouse does not respond to
the movements
Communication is not established
with the device used
It is impossible to print data
Run-time error
Carel reserves the right to modify the features of its products without prior notice.
The software described in this manual operates only with the DownLoad modules provided by Carel.
Fig. 17
Any persons passing this documentation and the relative software to others without the prior permission of Carel is liable to prosecution under copyright law.
CAUSE
SOLUTION
- Repeat the installation correctly specifying
destination disk drives
the disk-drive containing the program
diskette and the disk-drive where the
program is to be installed.
- There is not enough space for the
- At least 4MBytes of available space on
installation of the program on the disk.
the disk are necessary for the installation
of the program.
- The program is being "started" with an
- Make sure that in the command line of
icon that does not contain the correct
the icon the instructions are correct. Also
instructions
check the procedure for the execution of
the program.
- Erase the contents of the directory or
create a new one and repeat the
installation.
- Absence of the mouse driver
- Install the mouse driver using the
diskettes supplied with the device
- The serial port of the mouse has been
- Leave the serial port utilised by the
utilised to connect a line of the
mouse free by using the other serial
supervisor
ports for the lines of the supervisor
- The serial port configured is not
- Change serial port using the Options
correct: "serial communications error"
menu: Serial Comm.
- The serial port is already being used by
- Exit the application in question and
another application, e.g. a Fax program
re-start WinLog. Caution if the
application has replaced the standard
serial driver, WinLog will not be able to
establish serial communications
- Wrong serial address of the instrument
- Check that the serial address of the
Datalogger to be controlled by the
supervisor and the one selected in
WinLog are the same (See Serial address).
- The cables are not properly connected
- Check the connections of all cables and
or are not of the type indicated
make sure that the cables are of the type
indicated
- The instrument is OFF
- Check the power supply of the instruments
and of the RS485-RS232 converter
- The printer is not connected
- Make sure that the printer cable is
connected to the parallel port, that the
cable is of the type indicated, and that
the printer is on and On Line.
- The default Windows™ printer is not the
- Make sure that the printer connected to
one presently connected to the PC
the PC is the default printer
- The printer is not able to handle graphics
- This printer can not be used
- International selections not compatible
- Since the modification of the international
with the software.
selections (control panel-international
selections) influences the system operation,
it is possible that during execution of the
program a "run-time" error occurs.
Consequently, in case of problems,
English language (GB) selection is
suggested.