Checks Before Initial Start-Up; Field Setting - Panasonic U-8ME4XPQM Manuel D'installation

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 60

12.2. Checks before initial start-up

NOTE
Remark that during the first running period of the unit,
required power input may be higher than stated on the
nameplate of the unit. This phenomenon originates
from the compressor that needs elapse of a 50 hours
run in period before reaching smooth operation and
stable power consumption.
Make sure that the circuit breaker on the power supply
panel of the installation is switched off.
Attach the power wire securely.
Introducing power with a missing N-phase or with a
mistaken N-phase will break the equipment.
After the installation, check the following before switching on the
circuit breaker:
1
The position of the switches that require an initial setting
Make sure that switches are set according to your application
needs before turning the power supply on.
2
Power supply wiring and transmission wiring
Use a designated power supply and transmission wiring and
make sure that it has been carried out according to the
instructions described in this manual, according to the wiring
diagrams and according to local and national regulations.
3
Pipe sizes and pipe insulation
Make sure that correct pipe sizes are installed and that the
insulation work is properly executed.
4
Air tight test and vacuum drying
Make sure the air tight test and vacuum drying were completed.
5
Additional refrigerant charge
The amount of refrigerant to be added to the unit should be
written on the included "Added Refrigerant" plate and attached
to the rear side of the front cover.
6
Insulation test of the main power circuit
Measure the insulation resistance and check if the value is in
accordance with relevant local and national regulations..
7
Installation date and field setting
Be sure to keep record of the installation date on the sticker on
the rear of the upper front panel according to EN60335-2-40.
and keep record of the contents of the field setting.

12.3. Field setting

If required, carry out field settings according to the following
instructions. Refer to the service manual for more details.
Opening the switch box and handling the switches
When carrying out field settings, remove
the inspection cover (1).
Operate the switches with an insulated
stick (such as a ball-point pen) to avoid
touching live parts.
Make sure to re-attach the inspection cover (1) into the switch box
cover (2) after the job is finished.
Make sure that all outside panels, except for the panel
NOTE
on the electric box, are closed while working.
Close the lid of the electric box firmly before turning on
the power.
Installation manual
23
Location of the dip switches, LEDs and buttons
1
2
3
4
5
LED state
Throughout the manual the state of the LEDs is indicated as follows:
Setting the push button switch (BS1~5)
Function of the push button switch which is located on the outdoor
unit PCB (A1P):
BS1 MODE
BS2 SET
BS3 RETURN
BS4 TEST
BS5 RESET
The figure shows state of the LED indications when the unit is
shipped from the factory.
Check operation procedure
1
2
1
2
Single outdoor
Multiple
outdoor
system
LED H1~8P
Push button switches
BS1~BS5
DIP switch 1 (DS1: 1~4)
DIP switch 2 (DS2: 1~4)
1
2
DIP switch 3 (DS3: 1~2)
4
3
5
x
OFF
w
ON
c
Blinking
TEST:
C/H SELECT
MODE
HWL:
IND
MASTER
H1P
H2P
H3P
H4P
BS1
BS2
BS3
MODE
SET
RETURN
For changing the set mode
For field setting
For field setting
For test operation
For resetting the address when the wiring is changed or
when an additional indoor unit is installed
Turn the power on for the outdoor unit and the indoor unit.
Be sure to turn the power on at least 6 hours before operation in
order to have power running to the crankcase heater.
Make sure that transmission is normal by checking the LED
display on the outdoor unit circuit board (A1P). (If transmission
is normal, each LED will be displayed as shown below.)
LED
Micro-
display
computer
(Default
Ready
Indivi-
operation
status
Mode
/Error
dual
monitor
before
delivery)
HAP
H1P
H2P
H3P
c
x
x
w
unit system
Master
c
x
x
w
(a)
unit
Slave
c
x
x
unit
(a)
unit
1
Slave
c
x
x
unit
(a)
2
(a) The state of the H8P (multi) LED in a multi-system shows wich unit is the master
unit (w), slave 1 unit (c) or slave 2 unit (x).
Only the master unit is connected to the indoor units with interunit wiring.
L.N.O.P DEMAND
MULTI
SLAVE
H5P
H6P
H7P
H8P
BS4
BS5
TEST
RESET
Cooling/Heating
changeover
Bulk
Bulk
Low
(master)
(slave)
noise Demand Multi
H4P
H5P
H6P
H7P
H8P
x
x
x
x
x
x
x
x
x
w
x
x
x
x
x
c
x
x
x
x
x
x
U-8~16ME4XPQM
Urban Multi air conditioner
4PW40728-1

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

U-10me4xpqmU-12me4xpqmU-14me4xpqmU-16me4xpqm

Table des Matières