10.1.3. Electrical connection
Fig. 21: Connecting the cable plug
→
Loosen the screw ③ on the cable plug and remove the cable
plug.
NOTE!
Bent plug tabs will prevent the contact insert from being rein-
stalled properly, thereby resulting in functional failure!
• Carefully remove the contact insert and make certain the plug
tabs are not bent.
30
Item Part designation
1
Flange seal
2
Contact insert
3
Screw
4
Cap
5
Pressure ring
6
Flat seal
7
Collet chuck
8
Union nut
English
Types 2100, 2101, 2103
Option:Electricalpositionindicator
→
Loosen the screw in the cap ④ and remove the contact insert
②.
→
Guide the cable through the union nut ⑧.
→
Make the connection as shown for the circuit
(see "Fig. 22: Electrical circuit").
→
Max. connected loads:
5 A at 250 V AC
0.25 A at 250 V DC.
Fig. 22: Electrical circuit
→
Place the contact insert ② in the cap ④ and screw it on.
→
Screw on the cable plug with screw ③ making certain as you do
so that the flat seal ⑥ is securely seated.
→
Check the valve for function and leaks.
Configuration: 1
input
2 break contact
3 make contact