7.5
Min/Max Outputs
The S1/S2 Process Indicators are option-
ally available with 2 switching outputs, a
min and a max contact (see "Overview of
Options" on page E-82).
Limit value, hysteresis, switch-on delay,
min/max contacts and display flashing
are user definable (see "S.CON Menu" on
page E-108).
• Limit value as desired
• Hysteresis 0 – 9999 counts
• Switch-on delay 0 – 9999 s
• Normally closed (n/c) or
normally open contact (n/o)
• Display flashing (Y/no)
The present switching state is shown in
the display.
When the min or max setpoint is reached,
min or max, resp., flashes in the display.
After expiration of the switch-on delay,
min or max is displayed permanently, the
numbers of the digital display are flashing,
and the corresponding output is activated.
The display only flashes with Y FL set (see
page E-110).
E-99