CONTROL PANEL

1) GENERAL INFORMATION
The THALIA control panel comes with standard factory settings. Any change
must be made using the programmer with built-in display or universal handheld
programmer. The Control unit completely supports the EELINK protocol.
Its main features are:
-
Control of 1 or 2 24V BT motors
Note: 2 motors of the same type must be used.
-
Electronic torque control with obstacle detection
-
Limit switch control inputs based on motor selected
-
Separate inputs for safety devices
-
Built-in radio receiver rolling code with transmitter cloning.
The board has a terminal strip of the removable kind to make maintenance
or replacement easier. It comes with a series of prewired jumpers to make the
installer's job on site easier.
The jumpers concern terminals: 70-71, 70-72, 70-74. If the above-mentioned
terminals are being used, remove the relevant jumpers.
TESTING
The THALIA panel controls (checks) the start relays and safety devices (photo-
cells) before performing each opening and closing cycle.
If there is a malfunction, make sure that the connected devices are working
properly and check the wiring.
2) TECHNICAL SPECIFICATIONS
Power supply
Low voltage/mains insulation
Operating temperature range
Thermal overload protection
Dielectric rigidity
Motor output current
Motor relay switching current
Maximum motor power
Accessories power supply
AUX 0
Terminal
Definition
L
N
JP5
TRANSF PRIM
JP7
JP21
TRANSF SEC
10
11
14
15
20
CONTACT (N.O.)
21
AUX 3 - FREE
26
27
(Max. 24V 1A)
41
42
43
44
45
42
43
50
51
52
60
61
62
INSTALLATION MANUAL
220-230V 50/60 Hz*
> 2MOhm 500V
-20 / +55°C
Software
mains/LV 3750V~ for 1 minute
max. 7.5A+7.5A
10A
180W + 180W (24V
)
24V~ (demand max. 1A)
24V~safe
NO 24V
powered contact (max.1A)
LINE
Single-phase power supply
NEUTRAL
Transformer primary winding connection, 220-230V.
Board power supply:
24V~ Transformer secondary winding
24V= Buffer battery power supply
Connection motor 1. Time lag during closing.
MOT1 +
Check connections shown in Fig.J
MOT1 -
Connection motor 2. Time lag during opening.
MOT2 +
Check connections shown in Fig.J
MOT2 -
AUX 0 - 24V
AUX 0 configurable output - Default setting FLASHING LIGHT.
POWERED
2ND RADIO CHANNEL/ SCA GATE OPEN LIGHT/ COURTESY LIGHT command/ ZONE LIGHT command/ STAIR LIGHT/ GATE OPEN
ALARM/ FLASHING LIGHT/ SOLENOID LATCH/ MAGNETIC LOCK/ MAINTENANCE/ FLASHING LIGHT AND MAINTENANCE. Refer to
"AUX output configuration" table.
(MAX. 1A)
AUX 3 configurable output - Default setting 2ND RADIO CHANNEL Output.
CONTACT
2ND RADIO CHANNEL/ SCA GATE OPEN LIGHT/ COURTESY LIGHT command/ ZONE LIGHT command/ STAIR LIGHT/ GATE OPEN
ALARM/ FLASHING LIGHT/ SOLENOID LATCH/ MAGNETIC LOCK.
(N.O.)
Refer to "AUX output configuration" table.
+ REF SWE
Limit switch common
SWC 1
Motor 1 closing limit switch SWC1 (N.C.).
SWO 1
Motor 1 opening limit switch SWO1 (N.C.).
SWC 2
Motor 2 closing limit switch SWC2 (N.C.).
SWO 2
Motor 2 opening limit switch SWO2 (N.C.).
Limit switch control motor 1.
SW 1
For actuators with single-wire limit switch control.
Limit switch control motor 2.
SW 2
For actuators with single-wire limit switch control.
24V-
Accessories power supply output.
24V+
Tested safety device power supply output (photocell transmitter and safety edge transmitter).
24 Vsafe+
Output active only during operating cycle.
Common
IC 1 and IC 2 inputs common
Configurable command input 1 (N.O.) - Default START E.
IC 1
START E / START I / OPEN / CLOSE / PED / TIMER / TIMER PED
Refer to the "Command input configuration" table.
Configurable command input 2 (N.O.) - Default PED.
IC 2
START E / START I / OPEN / CLOSE / PED / TIMER / TIMER PED
Refer to the "Command input configuration" table.
AUX 3
Fuses
N° of combinations
Max.n° of transmitters that can be memorized 63
(*other voltages to order)
Usable transmitter versions:
All ROLLING CODE transmitters compatible with
2.1) VIRGO BAT BATTERY KIT (OPTIONAL)
3) TUBE ARRANGEMENT Fig.A
Arrange the electrical installation as shown in fig.A.
Keep the mains voltage connections definitely separate from the very low volt-
age connections (24V).
For this purpose, the operator is provided with appropriate fittings, indicated in Fig.A,
for a spiral flexible raceway with an inside diameter of 20:
- P1 input for mains power supply.
- P2/P3 inputs for safety devices and accessories.
For the mains power supply, use the appropriate cable clamp (Fig.A -"S").
4) TERMINAL BOARD WIRING Fig.K
WARNINGS - When performing wiring and installation, refer to the standards in
force and, whatever the case, apply good practice principles.
Wires carrying different voltages must be kept physically separate from each other,
or they must be suitably insulated with at least 1mm of additional insulation.
Wires must be secured with additional fastening near the terminals, using devices
such as cable clamps.
All connecting cables must be kept far enough away from the dissipater.
WARNING! For connection to the mains power supply, use a multicore cable
with a cross-sectional area of at least 3x1.5mm2 of the kind provided for
by the regulations in force. To connect the motors, use a cable with a cross-
sectional area of at least 1.5mm2 of the kind provided for by the regulations
in force. The cable must be type H05RN-F at least.
5) MOTOR CONNECTION AND LIMIT SWITCH ADJUSTMENT (Fig. J)
With the gate completely closed and open, rotate the corresponding cam until
you hear the relevant limit microswitch click and lock in position with the ap-
propriate screws.
Check the limit switches have activated correctly, starting some motorized open-
ing and closing complete cycles.
Description
220-230V 50/60 Hz*
NO contact (24V~/max.1A)
see Fig. K
4 billion
VIRGO SMART BT A
- 41