Inlet Drains For Distributors Connected To Atmospheric Steam Supplies - Carel ultimateSAM Mode D'emploi

Masquer les pouces Voir aussi pour ultimateSAM:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

A complete list of available kits, as well as information on other features, is
provided in Tab.3.b.
SAKT
x
2
1
ID prefix
Material:
F =
Iron
S =
SS
Type:
S =
Condensate separator
T =
Trap & strainer assembly
Size:
15 =
DN 15 flange
20 =
DN 20 flange
25 =
DN 25 flange
32 =
DN 32 flange
40 =
DN 40 flange
44=
1" pipe thread
50=
DN 50 flange
65=
DN 65 flange
84=
2" pipe thread
Region:
U =
North America
0 =
Other
---
---
Table 3.b provides a complete listing of all of the traps, strainers, and
other accessories available for the use with the ultimateSAM distributor. In
addition, the table provides information on the size and type of inlet-outlet
connection for each accessory.
Inlet-Outlet Connections
Size
"****FT**0*
****FS**0*
SAKT**15*0
Flange DN 15
SAKT**20*0
Flange DN 20
SAKT**25*0
Flange DN 25
SAKT**32*0
Flange DN 32
SAKT**40*0
Flange DN 40
SAKT**44*0
n/a
SAKT**50*0
Flange DN 50
SAKT**65*0
Flange DN 65
SAKT**84*0
n/a
Before installing an optional flanged trap and strainer kit, be sure that
the flange size matches the flange on the control valve. For an optional
threaded trap and strainer kit, be sure that the kit is properly sized for the
control valve. (Refer to the design manual for more information.)
Table 3.c lists the items and quantity of threaded fittings that are included
in each threaded trap and strainer kit. Flanged trap and strainer kits are
fully integrated. See figure 3.c, and section 9, figure 9.x -Trap, strainer, and
separators kits for more details.
Item List for SAKT*T**U0
Item (NPT)
SAKT*T44*0
Y-type stainer
F&T trap
Bushing F-M (size)
1 (¾"x1")
Elbow F-M (size)
Elbow F-F (size)
Nipple M-M (size)
2 (¾"x6")
1 (1"x3")
1 (1"x6")
Tee F-F-F (size)
Union F-F (size)
1 (¾"x¾")
xx
x 0
x
4
5
3
6
Material, Type, Region Codes
****FT**U*
****ST**U*
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
n/a
1" NPT Female
1"NPT Female
n/a
n/a
n/a
n/a
2" NPT Female
2" NPT Female
SAKT*T84*0
1 (1")
1 (1")
1 (¾")
1 (¾")
1 (¾"x2")
1 (¾")
1 (¾")
1 (1")
1 (2")
2 (¾"x6")
1 (2"x3")
1 (2"x6")
1 (1")
1 (2")
1 (¾"x¾")
3.3 Inlet drains for distributors connected to
atmospheric steam supplies
When used with an atmospheric humidifier, as shown in (Fig.3.e and Fig.
3.f ), an inlet trap may not be needed on the ultimateSAM distributor. In
a typical installation, the condensate in the connecting hose drains back
to the humidifier. In special situations when the condensate cannot drain
back to the humidifier, an inlet trap may be needed to prevent significant
amounts of condensate from entering the distributor.
Tab. 3.a
Tab. 3.b
Note: The adapters and steam hoses shown above are available as
options. The "P" drains are not provided as part of the ultimateSAM
system.
Tab. 3.c
17
Fig. 3.e
20° min.
Fig. 3.f
"ultimateSAM - user" +03U0070EF - rel. 2.0 - 20150301
ENG

Publicité

Chapitres

Table des Matières
loading

Table des Matières