2.2 Installing inlet adapters

If installing an inlet extension,
a.
Place the gasket on the face of the header's inlet.
b.
Using 7-8 Nm torque (5-6 ft lb), secure the extension adapter to the
header using the fasteners provided in the kit containing the inlet
adapter that will be secured to the extension.
Place the gasket on the face of the inlet of the header or extension.
Using 7-8 Nm torque (5-6 ft lb), secure the inlet adapter using the
fasteners provided. (Fig.2.b) If the inlet adapter is being attached to an
inlet extension, use the fasteners included in the extension kit to secure
the inlet adapter.
To connect the steam supply to the distributor, see section 4 for further
information.
2.3 Steam inlet connection between
ultimateSAM and valve flange
(SAKI******)
*Note: Not available in North American market.
Connection kits are available for ultimateSAM between the distributor
steam inlet and the valve flange.
These kits vary depending on the distributor steam inlet connection and
valve nominal diameter.
SAKIC
x
Family pre x
1
Pos.
Meaning
Type of connection
Nominal diameter
Region
The kits are available in AISI 316 stainless steel
The kit codes specified in Table 2.e comprise:
gasket (1);
flange (2);
adapter (6);
pipe (3 , 5);
joint (4);
Fig. 2.b
x
x x
0
2 3
Opt.
Description
64
1 1/2"
84
2"
94
2 1/2"
A
DN 15
B
DN 20
C
DN 25
D
DN 32
E
DN 40
F
DN 50
G
DN 65
U
North America
0
Other
Tab. 2.d
2
1
1
Code
SAKIC64A00
ultimateSAM valve connection kit (DN15 - 1" 1/2)
SAKIC64B00
ultimateSAM valve connection kit (DN20 - 1" 1/2)
SAKIC64C00
ultimateSAM valve connection kit (DN25 - 1" 1/2)
SAKIC64D00
ultimateSAM valve connection kit (DN32 - 1" 1/2)
SAKIC64E00
ultimateSAM valve connection kit (DN40 - 1" 1/2)
SAKIC64F00
ultimateSAM valve connection kit (DN50 - 1" 1/2)
SAKIC84B00
ultimateSAM valve connection kit (DN20 - 2")
SAKIC94C00
ultimateSAM valve connection kit (DN25 - 2" 1/2)
SAKIC94D00
ultimateSAM valve connection kit (DN32 - 2" 1/2)
SAKIC94E00
ultimateSAM valve connection kit (DN40 - 2" 1/2)
SAKIC94F00
ultimateSAM valve connection kit (DN50 - 2" 1/2)
SAKIC94G00
ultimateSAM valve connection kit (DN65 - 2" 1/2)
The minimum distance to allow for correct connection inside the
AHU is D= 100 mm (3.93 in) (Fig. 2.d)
The pipe x is used to pass through the insulating panel on the AHU.
15
"ultimateSAM - user" +03U0070EF - rel. 2.0 - 20150301
ENG
4
3
4
3
6
5
2
Fig. 2.c
Description
NOTE
also used with SA0*
D
D
Fig. 2.d
Tab. 2.e
AHU
AHU