Hitachi UTOPIA IVX PREMIUM Série Manuel D'installation Et De Fonctionnement page 31

Masquer les pouces Voir aussi pour UTOPIA IVX PREMIUM Série:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 119
Refrigerant piping & refrigerant charge
13.4.2 System Installation (examples)
Height Difference Between Indoor Units and Distributor

It is recommended to install all indoor units at the same height.
When the height difference between the indoor units due to build-
ing construction is necessary, this should be less than the value
indicated in the table. Install the branch pipe at the same height of
indoor units or lower, but never higher.
Indoor unit
Indoor
Height Difference between two
unit
indoors smaller than H
Smaller than 3 m
Premium
Standard
Installing Distributor

1 Install the Distributor supplied by HITACHI on request.
A tee can not be installed instead of a branch pipe.
2 Installing the distributor
Fix the branch pipe horizontally to the pillar, wall or ceiling. Pip-
ing must not be fixed rigidly to the wall as thermal expansion and
contraction can cause pipe fracture.
31
_PMML0251A_r2.indb 31
Branch pipe
O.U. (HP)
H (m)
3
3
4-10
10
3-10
3
PMML0251A rev.2 - 02/2013
Horizontal
To Indoor unit
To Indoor
Vertical
Unit
To Outdoor unit
Fixing the branch pipe to
the surface of pillar or wall
(pictures as example)
N O T E
Fix the piping from outside of insulation or inserting absorber be-
tween the pipe and a fixing metal.
3 Correct position of distributor (available also for quad instal-
lation)
This is the correct position:
G r e a t e r
than 0.5 m
Main pipe
Refrigerant direction
This is wrong position.
Refrigerant direction
Main pipe
Branch pipe
Branch pipe
(pictures as example)
Horizontal
Horizontal
Fixing the branch pipe to
ceiling or beam
Up
Branch pipe
Refrigerant di-
rection
Main pipe
Down
Branch pipe
Refrigerant di-
rection
Main pipe
06/02/2013 9:05:07

Hide quick links:

Publicité

Table des Matières
loading

Table des Matières