6.2 Troubleshooting chart
–
Solenoid valve
–
Aerator set/ (FL/CV)
–
Aerator set/ (FL/CV)
–
Aerator set/ (FL/CV)
–
Float switch
–
Trap
–
Magnetic safety
catch
Info - PRO status lights
Status
green
In function
flashing green
Wi-Fi active
flashing yellow
CAN bus + Wi-Fi active
magenta
Update
white
Reset
V1 / V2
green
Standby
blue
Flushing active
red
Error
orange
Warning
red & blue
Flushing active and current error
Water flow at the aerator
is low.
No clean spray cone from
aerator set.
No water from aerator.
Aerator dripping.
Float switch triggers fault
signal.
Odour!
Reversible cover doesn't
close flush with wall.
© www.kemper-olpe.de – 08.2021 / K410068903002-00 – 95 /108
Contamination before the fine
strainer on the solenoid valve.
Calcification of FL or
aerator.
Non-compliance with the
recommended replacement
interval.
Clogging!
FL installed wrong way round.
Solenoid valve doesn't close
properly.
Backflow in connected
drainpipe//trap due to
clogging.
No water in trap.
Anti-siphon trap not
fitted correctly.
Magnetic safety catch not
installed correctly/ only one of
the catches moved.
Plaster residue in the frame.
Guide bolts under the reversible
cover not inserted in the holes
provided in the FM frame.
Info - PURE status lights
V1 / V2
green
In function
yellow
Water exchange group selection
blue
Flushing active
red
Error
red & blue
Flushing active and current error
Interval time (h) + flush duration (min)
green
Selection
flushing green
Selection confirmed
Remove solenoid valve and
clean, replace if necessary, or
check FL/aerator.
Clean FL/aerator,
replace if necessary.
Install FL the right way round.
The aerator's outer gasket
must point in the direction of
flow (upwards).
Remove solenoid valve and
clean,
replace if necessary.
Check whether the drainpipe
was designed according to DIN
1986-100 in conjunction with
EN 752 and EN 12056.
Float switch
Check manually.
Check cable connection from
the float switch to the
controller.
Perform manual flushing.
Fit anti-siphon trap correctly.
Install magnetic safety catch
correctly/move both
catches into the same position.
Remove plaster residue from
the frame.
Insert guide bolts under the
reversible cover into the holes
provided in the FM frame.
EN