Assembly & Connection - Kemper KHS Hygiene Flush Box PRO Instructions D'installation Et D'utilisation

Masquer les pouces Voir aussi pour KHS Hygiene Flush Box PRO:
Table des Matières

Publicité

1.5 Technical data
PRO and PURE specifications (control unit)
Power supply
Event log memory capacity
Pollution degree
Protection class
Type
Overvoltage category
Altitude
LITE specifications (control unit)
Power supply
Event-entry storage
Contamination level
Note! Hot potable water!
Hot water must only be connected if cold water is connected to the other port of the Hygiene Flush Box.
Hot water shall only be flushed to avoid stagnation in distribution pipes (water exchange of non-circulating water;
<3 litres).
Note! Thermal disinfection!
If, during thermal disinfection, a flushing is carried out at 70 °C for 3 minutes on a KHS Hygiene Flush Box, this
must be precisely logged.
To do this on a KHS Hygiene Flush Box PURE or LITE, for temperature monitoring purposes, the reversible cover
must be opened and the trap cover removed so that the temperature of the exiting spray can be monitored.
To do this on a KHS Hygiene Flush Box PRO, for temperature monitoring purposes, the reversible cover must be
opened and a WLAN connection to the Hygiene Flush Box established. This allows the temperature to be monito-
red via the built-in flow and temperature sensor.
2 Assembly and connection
The following describes surface-mounted and flush-mounted installation, as well as the connection of feed and waste-water pipes and
the electrical connection.
type 1.Y (according to EN 60730-1)
© www.kemper-olpe.de – 08.2021 / K410068903002-00 – 25 /108
230 (±10 %) V AC
100 000 events
3
II with functional earth
III
max. 2000 MSL
24 V DC
depends on BMS
3
EN
62