General specification

Pressure rating
Max. flow pressure
Min. ambient temperature (storage)
Max. ambient temperature (storage)
Max. volume flow per FL for PWC
Max. volume flow per FL for PWH
Min. operating temperature PWC
Max. operating temperature PWH
Max. PWH flush duration per 24 hours
Max. rel. indoor humidity
Protection class
Weight with single port
Weight with double port
Nominal drainpipe diameter
Hygiene Flush Box dimensions (W x H)
Interference dimensions (W x H x D)
Reversible cover dimensions (W x H)
Max. depth adjustment with (flush-mounted)
mounting frame
Spacing of drinking water connections
Size of drinking water connection
Aerator set incl. flow limiter
Noise protection certification
Noise emission flush-mounted
Noise emission surface-mounted
* A cold drinking water flush (1 min) must be carried out immediately afterwards!
** The specified noise emissions (sound pressure level) represent guide values.
24 / 108 – K410068903002-00 / 08.2021 – © www.kemper-olpe.de

1.5 Technical data

1 water exchange group 33,8 dB(A) at 5l/min / 37,1 dB(A) at 10l/min**
2 water exchange groups 36,5 dB(A) at 5l/min / 38,1 dB(A) at 10l/min** dB(A)
1 water exchange group 43,7 dB(A) at 5l/min / 48,9 dB(A) at 10l/min**
2 water exchange groups 49,6 dB(A) at 5l/min / 49,9 dB(A) at 10l/min** dB(A)
If the surface or background changes, the values may differ.
(with PURE and LITE, only guaranteed by correct operation*) 10 min
DIN EN ISO 3822 class 1 to 30 l/min
10 PN
7 bar
0 °C
50 °C
15 l/min
10 l/min
10 °C
70 °C
65 %
IP44
6 kg
7 kg
40/50 DN
400 x 400 mm
400 x 480 x 98 mm
393 x 292 mm
65 mm
219 mm
3/4 " G
5/10/15 l/min