SUPPLEMENT
LED1(D023)
S006
S007
CN085
CN056
CN057
CN049
CN050
CN052
CN053
CN054
S002
S003
● Name And Function Of Each Switch On Outdoor Unit Control PC Board
• Mode Select switch
Changes to the cooling or heating mode. (Main outdoor unit is only usable.)
(3P, Black) (CN085)
During normal drive
When the cooling side is short-circuit, all indoor units change to cooling mode.
When the heating side is short-circuit, changes to all heating mode.
• Auto Address pin
Short-circuit for 1 second or longer.
(2P, White) (CN054)
When the short-circuit remains in effectfor more than 1 second during auto address, the auto
address is interrupted.
• Test Run pin
When set to short-circuit, changes to the test run mode.
(2P, White) (CN049)
(The test run mode is automatically cancelled after an hour.)
When short-circuit is cancelled, the test run mode is cancelled.
• RC socket
Connects to the outdoor unit maintenance remote control and the content of an alarm message
(3P, Blue) (CN077)
will be checked.
• Drive pin
When the pulse signal applied after short-circuit, all indoor units within the same series will be
(2P, White) (CN052)
operated.
• Stop pin
When the pulse signal applied after short-circuit, all indoor units within the same series will be
(2P, White) (CN053)
stopped.
(When set to short-circuit, the remote control from the indoor unit can not be operated.)
• Vacuum pin
Used for vacuuming the outdoor unit.
(2P, White) (CN050)
Socket for Snow Area
• Snow socket
Used for installing the snow sensor
(3P, Red) (CN057)
Silent Socket
• Socket for silent mode
Used for installing the external timer for the silent mode
(2P, White) (CN056)
CN077
CN072
LED2(D024)
S010
S005
S004
When opened, the auto address mode starts.
43
7-4. Auto Address Setting
Basic wiring diagram: Example (1)
• If link wiring is not used
(The inter-unit control wires are not connected to multiple refrigerant systems.)
Indoor unit addresses can be set without operating the compressors.
No. 1 (main outdoor unit)
settings
No. of indoor units
(10 units setting)
System address
(S004)
(system 1 setting)
0
(S002)
(S003)
ON
ON
(S005)
1
2
ON
ON
OFF
1
2
3
OFF
No. of
(S006)
(S007)
Unit
outdoor
Unit number
number
ON
ON
ON
ON
setting
units (3units
setting
1
2
3
(Unit No. 1)
1
2
3
setting)
OFF
(Unit No. 2)
OFF
Leave the socket that is
used to short-circuit the
Unit
terminal plug.
Outdoor Unit
No. 1
(CN072)
(Main)
Inter-outdoor unit
control wiring
Inter-unit control wiring
1-1
1-2
Indoor Unit
Remote controller
Case 1
(1) Automatic Address Setting from the Outdoor Unit
1.
To set the number of outdoor units, on the outdoor main unit control PCB set the No. of outdoor units DIP switch (S006) to
ON
ON
(3 units), and set the unit No. DIP switch (S007) to
1
2
3
OFF
2.
On the No. 2 (sub) unit control PCB, set the unit No. switch (S007) to
On the No. 3 (sub) unit control PCB, set the unit No. switch (S007) to
3.
On the outdoor main unit control PCB, check that the system address rotary switch (S002) is set to "1" and that the DIP
switch (S003) is set to
ON
ON
"0." (These are the settings at the time of factory shipment.)
1
2
OFF
4.
To set the number of indoor units that are connected to the outdoor unit to 10 on the outdoor main unit control PCB, set the
ON
ON
No. of indoor units DIP switch (S005) to
"1," and set the rotary switch (S004) to "0."
1
2
3
OFF
5.
Turn ON the power to the indoor and outdoor units.
6.
On the outdoor main unit control PCB, short-circuit the automatic address pin (CN054) for 1 second or longer, then release it.
(Communication for automatic address setting begins.)
* To cancel, again short-circuit the automatic address pin (CN054) for 1 second or longer, then release it.
The LED that indicates that automatic address setting is in progress turns OFF and the process is stopped. Be sure
to perform automatic address setting again.
(Automatic address setting is completed when LEDs 1 and 2 on the outdoor main unit control PCB turn OFF.)
7.
Operation from the remote controllers is now possible.
* To perform automatic address setting from the remote controller, perform steps 1 to 5, then use the remote controller and
complete automatic address setting.
● Refer to "Automatic Address Setting from the Remote Controller."
No. 2 (sub unit)
No. 3 (sub unit)
settings
settings
(S007)
(S007)
Unit
ON
ON
ON
ON
number
setting
1
2
3
1
2
3
OFF
OFF
(Unit No. 3)
Unit
Unit
No. 2
No. 3
(Sub)
(Sub)
Inter-outdoor unit
control wiring
1-3
1-10
Remote controller
communication wiring
Fig. 7-5
ON
(unit No. 1 – main outdoor unit).
1
2
3
ON
(unit No. 2).
1
2
3
ON
(unit No. 3).
1
2
3
44