OPERATING FUNCTIONS

In normal operation, the display shows the
status of the door or the number of the
current error.
To this end, set all dipswitches to OFF!
Displaying the position of the door
Move dipswitch 1 to ON.
Use the OPEN and CLOSE buttons (on the
front board) to select parameter 0.
Now set dipswitches 1 and 4 to ON.
The current position of the door is displayed.
If dipswitches 1-4 are set to ON, and you then
press OPEN and CLOSE on the front board, the
display shows the top end position.
Displaying the parameters
Move dipswitch 1 to ON.
Use OPEN to move to the next parameter.
Use CLOSE to move to the previous parameter.
Hold down OPEN and CLOSE together (on the
front board) to move to parameter 0.
Modifying the selected parameters (scroll)
Move dipswitch 1 to ON.
Use the OPEN and CLOSE buttons (on the
front board) to select the parameter you wish
to modify.
Now set dipswitches 1 and 4 to ON. Use
OPEN on the front board to increase the
parameter number.
Use CLOSE on the front board to decrease the
parameter number.
Save the selected parameters - set dipswitch
4 to OFF.
Deleting a parameter
If dipswitches 1 and 4 are set to ON, and you
press OPEN and CLOSE together, the selected
parameter is deleted.
Parameter quick edit
Hold the button down for 1 sec. The value
changes by 10 units/sec.
Hold the button down for 3 sec. The value
changes by 100 units/sec.
Automatic Closing
If the automatic close function is enabled, the door closes after the time set
in parameter 41 has expired with the door in the end position. Refer to the
parameters list. Actuating the Stop function immediately stops the door when
it is closing.
If the door is in the top end position and the transit photocell is obscured or the
OPEN button is pressed, the automatic close time is reset.
Deleting the Eprom (Reset - factory settings)
After 2 seconds the Eprom is restored to its
factory settings
(for the default values of the parameters, see
the list of parameters).
After this, the control unit reboots.
Setting EE_1 enables the inverter parameters.
For inverter operation, you must reset P70 as
specified, all the other parameters must be
set anew in relation to the design. Refer to the
parameters list.
OPERATIONAL DISPLAY TYPE
End position adjustment - flashing
TOP end position
BOTTOM end position
Partial open
DISPLAY end positions - STANDARD - P5
= 0
TOP end position
BOTTOM end position
Partial open
DISPLAY end positions - Text - P5 = 1
TOP end position
BOTTOM end position
Partial open
DISPLAY door movement - Text - P5 = 2
OPEN DOOR
CLOSE DOOR
OPERATIONAL DISPLAY TYPE
The input states are displayed as follows:
set parameter P29 to 1.
CLOSE button
OPEN button
Jog button or pull-cord
Transit photocell
Radio signal
Emergency stop input
Lower sensitive edge
English – 7