Mounting and
operating instructions
Example telegram
(in the example, the sensor has the address 1)
Master telegram
Designation
1. Byte
Address
2. Byte
Length
3. Byte
Command
4. Byte
Check sum
8.5.23

„Meas. value hold" function

Command (Byte 3): decimal 82; hexadecimal 0x52
Parameter:
D0 = 0: Measuring value Hold off
D0 = 1: Measuring value Hold
Reply (Byte 3):
decimal 89; hexadecimal 0x59
Parameter:
no
If this function is activated, the last valid measured value is transmitted at the analogue output when no object is in
the measuring range (OK LED = OFF), . The switching output also maintains its status (if set).
The current value is only displayed again when an object is within the measuring range (OK LED = ON).
FT 50 RLA Disctance sensor - GB - 068-13671 - 20.04.2009-05
Decimal
Hex.:
129
81
4
04
63
3F
58
3A
Sensor's reply telegram
Designation
1. Byte
Address
2. Byte
Length
3. Byte
Reply
4. Byte
Function 1
5. Byte
6. Byte
Function 2
7. Byte
8. Byte
Function 3
9. Byte
10. Byte
Characteristic
curve 4 mA point
11. Byte
12. Byte
Characteristic
curve 20 mA point
13. Byte
14. Byte
Switching thres-
hold Q
15. Byte
1
16. Byte
Scanning zone Q
17. Byte
18. Byte
Switching thres-
hold Q
19. Byte
2
20. Byte
Scanning zone Q
21. Byte
21. Byte
Check sum
Parameter format
7 bit data byte
Decimal
Hex.:
129
81
21
15
89
59
32
20
1
01
48
30
48
30
55
37
1
01
0
00
0
00
63
3F
63
3F
0
00
0
00
0
00
1
0
00
0
00
63
3F
63
3F
2
63
3F
101
65
77