Example telegram
(in the example, the sensor has the address 1, Q
Master telegram
Designation
1. Byte
Address
2. Byte
Length
3. Byte
Command
4. Byte
Data
5. Byte
Check sum
8.5.18

Distance measured values

Command (Byte 3): decimal 65; hexadecimal 0x41
Parameter:
no
Reply (Byte 3):
decimal 89; hexadecimal 0x59
Parameter:
Data
Reads out the current distance to the object (raw data). Altered characteristic settings (4 mA point, 20 mA point, Min,
Max, autom. centre ...) are not taken into account. The analogue output is not affected, it always transmits measured
operating values.
Example telegram
(in the example, the sensor has the address 1)
Master telegram
Designation
1. Byte
Address
2. Byte
Length
3. Byte
Command
4. Byte
Check sum
8.5.19

Operating measured values

Command (Byte 3): decimal 73; hexadecimal 0x49
Parameter:
no
Reply (Byte 3):
decimal 89; hexadecimal 0x59
Parameter:
Data
The current measured values and switching output recognition are read whilst taking into account the settings which
alter the characteristics (4 mA point, 20 mA point, Min., Max., autom. centre ...).
74
is set to high)
1
Decimal
Hex.:
129
81
5
05
81
51
1
01
84
54
Decimal
Hex.:
129
81
4
04
65
41
68
44
Sensor's reply telegram
Designation
1. Byte
Address
2. Byte
Length
3. Byte
Reply
4. Byte
Check sum
Parameter format
12 bit data item Data 3
Sensor's reply telegram
Designation
1. Byte
Address
2. Byte
Length
3. Byte
Reply
4. Byte
Data
5. Byte
6. Byte
Check sum
Parameter format
12 bit data item:
Data 3 with switching output recognition
FT 50 RLA Disctance sensor - GB - 068-13671 - 20.04.2009-05
Mounting and
operating instructions
Decimal
Hex.:
129
81
4
04
89
59
92
5C
Decimal
Hex.:
129
81
6
06
89
59
64
40
0
00
30
1E