Dimensions in mm
X = fixing dimensions
100 A 3-pole
100 A 6-pole
125 A 3-pole
16
Switches, GHG 981,
industrial design up to 250 A, 3 and 6-pole
1�6
Safety switch 100 A; GHG 981 0029 - 3-pole; GHG 981 0030 - 6-pole
Rated voltage:
Rated current:
Perm� short circuit back-up fuse:
Switching capacity AC 23 A:
Cable entries (standard version):
suitable cables and test torques of the pressure screw
Cabel entry:
Seal 1+2+3
min�
max� (1)
(Ø mm / Nm)
Seal 1+2
min�
max� (1)
(Ø mm / Nm)
Seal 1
min�
max� (1)
(Ø mm / Nm)
Pressure screw (Nm)
(1)
The tests of clamping ranges and torque values were performed with metal mandrel� The clamping range can
vary by using cables with different manufacturing tolerances and material properties� Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance
work on the cable entry�
Terminals:
Test torque terminals:
Weight (standard version):
1�7
Safety switch 125 A; GHG 981 0027 - 3-pole
Rated voltage:
Rated current:
Perm� short circuit back-up fuse:
Switching capacity AC 3:
Cable entries (standard version):
suitable cables and test torques of the pressure screw
Cabel entry:
Seal 1+2+3
1 2
3
(Ø mm / Nm)
Seal 1+2
1 2
3
(Ø mm / Nm)
Seal 1
1 2
3
(Ø mm / Nm)
Pressure screw (Nm)
(1)
The tests of clamping ranges and torque values were performed with metal mandrel� The clamping range can
vary by using cables with different manufacturing tolerances and material properties� Please use a suitable
combination of seals in the intermediate area, so that the cap nut can be tightened in future maintenance
work on the cable entry�
Terminals:
Test torque terminals:
Weight (standard version):
690 V, 50/60 Hz
100 A
up to U
400 V
N
160 A/gL
100 A
3-pole version
2 x M50 + 1 x M25
M25
8�0 / 1�5
10�0 / 2�0
10�0 / 2�3
13�0 / 2�6
13�5 / 1�3
17 �5 / 2�3
3�0
1 x 6 - 50 mm² observe current load.
6,0 Nm
3-pole - approx� 6�50 kg
690 V, 50/60 Hz
125 A
up to U
400 V
N
200 A/gL
125 A
3-pole version
2 x M63 + 1 x M25
M25
min�
8�0 / 1�5
max� (1)
10�0 / 2�0
min�
10�0 / 2�3
max� (1)
13�0 / 2�6
min�
13�5 / 1�3
max� (1)
17 �5 / 2�3
3�0
2 x 4�0 - 70 mm² observe current load.
max� 1 x 120 mm² (Use cable lugs supplied with switches)
5�0 Nm
3-pole - approx� 16�00 kg
GB
up to U
500 V
up to U
690 V
N
N
–-
125 A/gL
100 A
100 A
6-pole version
4 x M50 + 1 x M25
M50
24�0 / 6�0
28�0 / 7�0
28�0 / 5�0
35�0 / 7�0
7�5
6-pole - approx� 12�50 kg
up to U
500 V
up to U
690 V
N
N
–-
160 A/gL
125 A
110 A
M63
29�0 / 12�0
35�0 / 12�0
36�0 / 12�0
41�0 / 13�0
7�5