Technical Specifications - Ducati Energia REGO 5 Manuel D'instruction

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

17) TECHNICAL SPECIFICATIONS

REGO 5/7/12 step power circuit
Supply voltage
Rated frequency
Input power
Protection
Current input
Rated current
Operating range
Overload
Consumption
Measurement and control data
Type of voltage and current
measurement
Power factor control
Step re-connection time lag
Relay outputs
Number of outputs
Contact status
Nominal contact capacity
Voltage rating
Alarm relay
Nominal insulation voltage
Max. relay switching power
Measuring precision
Power factor
Active voltage (UFF)
Line current
94
380÷415V±10%
220÷240V±10%
50 or 60Hz (measured and autonomously
set by the controller)
8VA max. (REGO 5)
15VA max. (REGO 7/12)
Internal fuse 250mA T curve. To protect the instrument
from permanent overvoltage, the user should install
an external fuse (we recommend 200mA)
5A
0.2...5A
3 In for 10s
0.5VA max. (REGO 5)
1.5VA max. (REGO 7/12)
true effective value ( true RMS )
0.80 inductive ÷ 0.80 capacitive
5...255s
5/7/12
N/O
5A - 250V
250Vac
1 N/C contact (3A-250V).
When controller is off, the contact is N/O.
3kV/1minute
2200W or 1500W - Cosϕ 0.5 250V
±2%
±2%
±2% value read for I>200mA (CT secondary winding)

Publicité

Table des Matières
loading

Produits Connexes pour Ducati Energia REGO 5

Table des Matières