12.3 PROCEDURE FOR CHECKING THE EFFICIENCY OF THE
SINGLE STEPS
Press DATA + M to access the menu pertaining to the procedure for
checking the powers of the capacitor steps (the display will show "ChP"
and M will flash).
Pressing the M key will cause REGO to switch off all the banks and
start the procedure for measuring the power of all the steps (the cycle
will be launched three times to provide a better measurement). If REGO
detects differences of more than 25% in the power that was associated
with the step during the previous auto-acquisition procedure, the
corresponding LED will flash. At the same time the letters "rSt" will
appear on the display
and the user must disable the step by pressing ALARM/RESET; if this
key is not pressed within a few seconds, the operation will be terminated
without any effect taking place. Once the check is completed, REGO
will function as before, with the exclusion of any steps detected to be
faulty, whose LEDs will continue flashing to signal their status of
unavailability.
12.4 PROCEDURE FOR ENABLING/DISABLING OUTPUT RELAYS
IN THE AUTOMATIC OPERATING MODE
The user can decide which relays the controller must not use in the
automatic mode.