Ducati Energia REGO 5 Manuel D'instruction page 75

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

PARAMETER DESCRIPTION
(10.1) Fr
Measured mains frequency
Only an indication
(10.2) COS
Power factor to be achieved within
the system.
(10.3) UFF
Voltage rating of controller.
(10.4) IL
Mains C.T. ratio.
Example: with CT 100/5 set 20
Example: with CT 200/5 set 40
(10.5) Con
Type of connection of controller to mains.
(10.6) SUP
Setting of terminal used to power
the controller.
(10.7) FAS
Auto-adjustment of mains C.T. direction:
On=auto-adjustment
blo= fixed direction
(10.8) ACq
Acquisition of step powers:
no = no acquisition procedure
AUt = automatic acquisition
Pr = manual setting
(10.9) s:s:s:
Display of set logic
74
Table 2: Setup parameters
RANGE
DEFAULT
50 or 60 Hz
-/-.
0.8IND÷0.8CAP
0.95
230 or 400
400
1...3000
FF1
FF1
FF2
F-n
U1 (230V)
U2 (400V)
U2
On
On
blo
no
no
AUt
Pr
1:1:1
-/-
1:2:2
1:2:4

Publicité

Table des Matières
loading

Produits Connexes pour Ducati Energia REGO 5

Table des Matières