10.6 "SUP" = Setting of terminal used to power the controller.
"SUP" is displayed in turn with the default value "U2".
The user can change this parameter using the L or M key
(possible settings: U1/230V, U2/400V).
DO NOT CHANGE THIS PARAMETER IF THE CONTROLLER
IS INSTALLED ON A DUCATI ENERGIA POWER FACTOR
CORRECTION SYSTEM.
Press DATA to go on to the next parameter
10.7 "FAS" = Activation or deactivation of automatic adjustment of
mains C.T. direction.
"FAS" is displayed in turn with the default value "0n" (auto-
adjustment enabled).
The parameter can be changed using the L or M key (possible
settings: On/auto-adjustment, blo/C.T. direction fixed).
DO NOT CHANGE THIS PARAMETER IF THE CONTROLLER
IS INSTALLED ON A DUCATI ENERGIA POWER FACTOR
CORRECTION SYSTEM.
10.8 "ACq" = Menu for launching the procedure for acquiring the power
of single steps and setting their switching logic.
"ACq" is displayed in turn with the default value "no".
The parameter can be changed using the L or M key and
confirming by pressing DATA; the possible settings are: