DO NOT CHANGE THIS PARAMETER IF THE CONTROLLER
IS INSTALLED ON A DUCATI ENERGIA POWER FACTOR
CORRECTION SYSTEM.
Press DATA to go on to the next parameter
10.4 "IL" = Mains C.T. ratio.
The "IL" parameter is displayed in turn with the value previously
set by the user.
The value can be changed using the L or M key.
Setting examples:
C.T. 300/5 IL=60; C.T. 350/5 IL=70; C.T. 400/5 IL=80
Ex.
Press DATA to go on to the next parameter
10.5 "COn" = Type of connection of controller to mains.
"COn" is displayed in turn with the default value "FF1".
The user can change this parameter using the L or M key
(possible settings: FF1, FF2, F-n - see chap 5 - Page 59).
DO NOT CHANGE THIS PARAMETER IF THE CONTROLLER
IS INSTALLED ON A DUCATI ENERGIA POWER FACTOR
CORRECTION SYSTEM.
Press DATA to go on to the next parameter