steps of 10-10-20-20-40 the parameters should be set as follows:
Pro = 26 (see Table 1 - Page 72)
PFC = 10.
Press DATA to confirm and go on to the next parameter.
SWITCHING LOGICS
The controller can adopt one of three logics to switch the capacitor
banks in and out of service in order to achieve and maintain the set
cosϕ, i.e.:
LINEAR LOGIC
This logic is identified by the code 1:1:1 and presupposes the condition
that all capacitor banks have equal powers. Given a situation such as
the one illustrated in the table,
Bank No.
1
Status
OFF
the controller will switch on bank no. 5 if a bank needs to be switched
into service and switch off bank no. 2 if one needs to be switched off.
This will ensure that all the banks will work and as a result component
wear will be evenly distributed among them.
GEOMETRIC LOGIC
It is identified by the code 1:2:4 and presupposes the condition that
each bank has a power equal to or at most double the power of the
one that precedes it. Assuming that the banks have powers as shown
in the table,
70
2
3
ON
ON
4
5
ON
OFF
6
OFF