2-3. Single UPS Installation

Installation and wiring must be performed in accordance with the local electric laws/regulations and execute the
following instructions by professional personnel.
6)
Make sure the mains wire and breakers in the building are enough for the rated capacity of UPS to avoid the
hazards of electric shock or fire.
NOTE: Do not use the wall receptacle as the input power source for the UPS, as its rated current is less than the UPS's
maximum input current. Otherwise the receptacle may be burned and destroyed.
7) Switch off the mains switch in the building before installation.
8) Turn off all the connected devices before connecting to the UPS.
9) Prepare wires based on the following table:
Model
E4 LCD Evolution 10K TM
E4 LCD Evolution 10K STM
E4 LCD Evolution 15K TM
E4 LCD Evolution 15K STM
E4 LCD Evolution 20K TM
E4 LCD Evolution 20K STM
E4 LCD Evolution 30K TM
E4 LCD Evolution 30K STM
NOTE 1: The cable for 10K/10KL should be able to withstand over 63A current. It is recommended to use
8AWG or thicker wire for safety and efficiency.
NOTE 2: The cable for 15K/15KL should be able to withstand over 75A current. It is recommended to use
6AWG or thicker wire for safety and efficiency.
NOTE 3: The cable for 20K/20KL should be able to withstand over 100A current. It is recommended to use
6AWG or thicker wire for safety and efficiency.
NOTE 4: The cable for 30K/30KL should be able to withstand over 140A current. It is recommended to use
4AWG or thicker wire for safety and efficiency.
NOTE 5: The selections for color of wires should be followed by the local electrical laws and regulations.
10) Remove the terminal block cover on the rear panel of UPS. Then connect the wires according to the following
terminal block diagrams: (Connect the earth wire first when making wire connection. Disconnect the earth wire last
when making wire disconnection!)
INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 06 14 AA 59 203 46
Wiring spec (AWG)
Input
Output
8 / 16
8 / 16
8 / 16
8 / 16
6 / 16
6 / 16
6 / 16
6 / 16
6 / 25
6 / 25
6 / 25
6 / 25
4 / 35
4 / 35
4 / 35
4 / 35
Battery
Ground
8 / 16
8 / 10
8 / 16
6 / 16
6 / 16
6 / 16
6 / 25
6 / 16
6 / 25
4 / 35
4 / 25
4 / 35
62