Les langues disponibles

5. Storage and Maintenance

5-1. Storage

Before storing, charge the UPS at least 7 hours. Store the UPS covered and upright in a cool, dry location. During
storage, recharge the battery in accordance with the following table:

Storage Temperature

-25°C - 40°C
40°C - 45°C

5-2. Maintenance

The UPS system operates with hazardous voltages. Repairs may be carried out only by qualified maintenance
personnel.
Even after the unit is disconnected from the mains, components inside the UPS system are still connected to
the battery packs which are potentially dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries and verify that no
current is present and no hazardous voltage exists in the terminals of high capability capacitor such as
BUS-capacitors.
Only persons are adequately familiar with batteries and with the required precautionary measures may
replace batteries and supervise operations. Unauthorized persons must be kept well away from the batteries.
Verify that no voltage between the battery terminals and the ground is present before maintenance or repair.
In this product, the battery circuit is not isolated from the input voltage. Hazardous voltages may occur between the
battery terminals and the ground.
Batteries may cause electric shock and have a high short-circuit current. Please remove all wristwatches,
rings and other metal personal objects before maintenance or repair, and only use tools with insulated grips and
handles for maintaining or repairing.
When replace the batteries, install the same number and same type of batteries.
Do not attempt to dispose of batteries by burning them. This could cause battery explosion. The batteries
must be rightly deposed according to local regulation.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin and eyes. It may be toxic.
Please replace the fuse only with the same type and amperage in order to avoid fire hazards.
Do not disassemble the UPS system.
INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
95
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 06 14 AA 59 203 46
Recharge Frequency
Every 3 months
Every 2 months
Charging Duration
1-2 hours
1-2 hours