5. Storage and Maintenance

5-1. Storage

Before storing, charge the UPS for at least 7 hours. Store the UPS covered and upright in a cool, dry
location. During storage, recharge the battery in accordance with the following table:
Storage Temperature
From -25°C to 40°C
INFOSEC UPS SYSTEM – 15, Rue du Moulin – 44880 Sautron – France – www.infosec-ups.com
49
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 10 19 AA 59 204 31
Fault code is shown as 43. The
icon
lights on LCD
display and alarm beeps
continuously.
Fault code is shown as 14, the
icon
lights on the LCD
display, and the alarm beeps
continuously.
Other fault codes are displayed
and the alarm sounds
continuously.
Battery backup time is shorter
than nominal value
The icons
and
the LCD display and the alarm
beeps every second.
Recharge Frequency
Every 3 months
The UPS has been in
overload too long and
becomes faulty. The UPS
shuts down automatically.
The UPS shuts down
automatically because a
short circuit occurred on
the UPS output.
A UPS internal fault has
occurred.
Batteries are not fully
charged
Battery defect
Fan is locked or not
flash on
working; or the UPS
temperature is too high.
Charging Duration
1-2 hours
first. Then
shut down
the UPS
and
restart it.
Remove
excess
loads
from UPS
output
and
restart it.
Check the
output's
wiring and
that
connected
devices
are in
short
circuit
status.
Contact
your
dealer
Charge
the
batteries
for at least
7 hours
and then
check
their
capacity.
If the
problem
persists,
consult
your
dealer.
Contact
your
dealer to
replace
the
battery.
Check the
fans and
notify your
dealer.