5
Electrical installation
Power terminals
Motor connection
5.2.2
Motor connection
Fig. 5−3
Motor and motor holding brake connection
Motor cables
Use low−capacitance motor cables. Capacitance per unit length:
ƒ
–
Core/core: max. 75 pF/m
–
Core/shield: max. 150 pF/m
Length: max. 50 m, shielded
ƒ
The cross−section of the motor cables are selected according to the motor
ƒ
standstill current (I
rated motor current (I
Length of the unshielded ends: 40 ... 100 mm (depending on the cable
ƒ
cross−section)
Lenze system cables meet these requirements.
ƒ
Use the ECSZS000X0B shield mounting kit for EMC−compliant wiring.
ƒ
,
Mounting instructions for ECSZS000X0B shield mounting
Here you can find more information on wiring according to EMC.
110
) when using synchronous motors or according to the
0
) for asynchronous motors.
N
l
ECSXA010
EDKCSDX064 DE/EN/FR 3.0