AVENTICS | ED07 | R414001671–BAL–001–AE | English
Missing seals and plugs will lead to non-compliance with the IP65 protection
class!
Liquids and foreign objects could penetrate the device and plug connections and
destroy the electronics.
O Use IP65 protection class plug-type connections.
O Make sure that the seals are integrated in the plug and not damaged.
O Make sure that all plugs are mounted before starting the system.
To operate the ED07 pressure regulator, you must supply the device with compressed
air, connect the 24 V DC supply voltage, and control the device with a set point.
The actual value (-) and set point (-) are always connected to 0 V. The
following applies for all devices with 0... 10 V voltage control: If the analog
trigger signal is not electrically isolated, please heed the line resistances to
minimize set point/actual value drifting and the controlled pressure.
Use a shielded line to connect XPC, X2M, and X2N. The shield must be
connected to the plug housing.
O Please heed the following tables containing the plug assignments for the
different series.
M12 integrated XPC plug, male, 5-pin
Pin 1
4
3
Pin 2
5
Pin 3
Pin 4
1
2
Pin 5
M12 integrated XPC plug, male, 5-pin
Pin 1
4
3
Pin 2
5
Pin 3
Pin 4
Pin 5
1
2
M12 integrated socket X2M, female, 5-pin
Pin 1
3
4
Pin 2
5
Pin 3
Pin 4
2
1
Pin 5
M12 integrated socket X2A, female, 5-pin
Pin 1
3
4
Pin 2
5
Pin 3
Pin 4
2
1
Pin 5
M12 integrated socket X2N, female, 5-pin
Pin 1
3
4
Pin 2
5
Pin 3
Pin 4
2
1
Pin 5
1) internally connected with contact X1S Pin 3.
NOTICE
24 V DC
Set point (+): current 0/4...20 mA or
voltage 0...10 V DC
0 V
Actual value (+): current 0/4... 20 mA or
voltage 0...10 V DC
FE
24 V DC
not assigned
0 V
not assigned
FE
Switch output for "Pressure reached"
Set point (+): current 0/4...20 mA or
voltage 0...10 V DC
1)
0 V
Actual value (+): current 0/4... 20 mA or
voltage 0...10 V DC or
10 V DC constant
FE
not assigned
Set point (+): current 0/4...20 mA or
voltage 0...10 V°DC
0 V
Actual value (+): current 0/4... 20 mA or
voltage 0...10 V°DC
FE
24 V DC
not assigned
1)
0 V
External sensor inlet: current 4...20°mA or
voltage 0...10 V°DC
FE
O Make sure before connecting the plugs that all seals and caps are included and
not damaged.
O Only use pre-assembled and tested plugs and cables,
O Protect the supply voltage with an external M 2.5 A fuse.
As the 0 V lines are linked in the case of the X2M and X1S connections, as
well as X2N and X1S, you must ensure that all the plug-type connections
are correctly poled. Short circuiting occurs due to pole confusion of the
supply voltage or set point voltage.
For devices controlled via potentiometer, integrated plug X1S and integrated socket
X2M:
O Connect the lines to the X2M integrated socket
Schaltausgang
1
2
3
4
5
00122911
7
Commissioning the EV07 pressure
regulator
Risk of destruction by water!
Water entering the device destroys the electronics.
O Ensure that the compensation port is sealed.
O Ensure that the four mounting screws are tightened with the correct torque.
O Never open the two fastening screws on the housing cover.
Prior to commissioning the EV07 pressure regulator
Attach base plate pneumatic connections
Depending on the application, the base plate is a
single subbase or base plate for stacking assembly.
1. Connect the supply line to inlet connection°1 on
2. Connect the outlet line to the output connection
3. Always connect a silencer or line for restricted
39
41
40
00121339
Danger caused by escaping compressed air!
Device is operating under pressure. On opening the additional input connection
(41) on the base plate, the seal screw can be hurled into the surrounding area and
may cause bodily harm and material damage.
O Never undo the seal screw during operation.
O Only connect another input connection when no pressure is supplied.
Exhaust 3 (40) in the single subbase must not be sealed by a screw.
O Always mount the exhaust on an appropriate silencer (see Chapter 13
„Accessories") or line for restricted exhaust.
Output pressure -1 bar...+1 bar:
On the ED07 pressure regulator with the pressure range -1 bar...+1 bar
a vacuum must be connected to exhaust 3.
Switching on the pneumatic and electrical supplies
Proceed as follows to commission the ED07 pressure regulator:
1. First switch on the pneumatic supply.
2. Then switch on the 24 V DC supply voltage.
Setting the set point
O Enter the desired set point in the controller or potentiometer.
O Please observe Chapter „Selecting the correct supply pressure".
as illustrated in the figure opposite.
Voltage can now be supplied to the ED07 pressure
regulator and the set point adjusted on the
potentiometer.
NOTICE
the base plate (39).
(unlabeled connection) on the opposite side.
exhaust to exhaust 3 (40).
CAUTION
11