Technical Data; Safety Instructions - Eaton CROUSE-HINDS Série Mode D'emploi

Fiches de 63 a pour atmosphères explosives, 4 pôles, 5 pôles
Masquer les pouces Voir aussi pour CROUSE-HINDS Série:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

2

Safety instructions

They are not suitable for Zone 0
and Zone 20 hazardous areas.
The temperature class and
explosion group marked on the
apparatus shall be observed.
The electrical connection of the device may
only be carried out by skilled staff
(IEC/EN 60079-14).
Modifications to the plugs and sockets or
changes of their design are not permitted.
They shall be used for their intended purpose
and in perfect and clean condition.
To ensure adherence to the temperature class
stated on the type label of the apparatus, the
permissible ambient temperature, the rated
terminal cross section and the self heating
of the apparatus that is mainly due to the
power dissipation shall be taken into account
(test criterion for the self heating is an
overload of 10%).
Prior to taking the plugs and sockets into
operation, they will have to be checked in
accordance with the instruction as per
section 6.
For replacement and repair only genuine
COOPER CROUSE-HINDS spare parts shall
be used.
Observe the national safety rules and
regulations for prevention of accidents as
well as the safety instructions included in
these operating instructions and set in italics
the same as this text!
6
Explosion protected plug 63 A, GHG 534
1

Technical data

Marking acc. to 94/9/EC:
EC type examination certificate:
Rated voltage:
GHG 534 -
4-pole
GHG 534 -
5-pole
(Special voltages and various contact-marking are possible on request)
Rated curret:
Back-up fuse:
without thermal protection
with thermal protection
Perm. ambient temperature:
Perm. storage temperature in original packing:
Protection category acc. to IEC/EN 60529
with closed and secured hinged cover as well
as combinations properly plugged together
Insulation class acc. to IEC/EN 61140:
Cable entry:
Plug GHG 543/531
Supply terminal
Plug GHG 534
Test torques:
Terminals plug
Weight:
Plug
EEx de II C T6
PTB Nr.Ex-86.B.1021
up to 690 V, 50/60 Hz
up to 500 V, 50/60 Hz
max. 63 A
GHG 534
63 A
80 A gL
-20 °C to +40 °C (catalogue version)
(Special versions permit deviating temperatures)
-20 °C to +40 °C
IP 66 (catalogue version)*
I - is complied with by devices
(catalogue version)
Ø 19 - 28 mm
Cross section
1 x 4.0 - 16 mm
2
2.5 Nm
(catalogue version)
approx. 2.6 kg
GB

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Crouse-hinds ghg 534

Table des Matières