NOTE
A parameterization error can be displayed during reconfiguration of PROFINET to EtherNet/IP
or Modbus TCP in connection with changing the BusAdapter type. You can only remedy the
parameterization error with a reset to factory settings and reconfiguration with MFCT. You
can find more information in the MultiFieldbus function manual
(https://support.industry.siemens.com/cs/us/en/view/109773209).
6.6
Transfer the configuration
The "Transfer configuration" area offers you the following options:
• Loading the project to the MF device
• Exporting the configuration for use in other engineering tools.
Loading the project in the MF device
To transfer the MF project to the MF device, follow these steps:
1. Select the "Transfer the project to the MF device" check box.
2. Click the "Start scan" button to search via the preset network interface for MF devices for
the project download. Devices without MultiFeldbus support cannot be selected and are
grayed out.
3. Select an MF device and start the download to the MF device using the "Start
transfer/export" button.
MultiFieldbus Configuration Tool (MFCT)
Configuration Manual, 03/2024, A5E53511456-AA
MultiFieldbus configuration
6.6 Transfer the configuration