Hitachi RPI-8.0-FSN3E Serie Manuel D'installation Et De Fonctionnement page 15

Table des Matières
Les langues disponibles

Les langues disponibles

  • FRANÇAIS, page 35
UNITS INSTALLATION

Suction Air Filter Servicing
Air Filter Support
Removing Direction
3.1.4 Fan Performance Curve
Std. Air Filter Pressure Lost
"●" Rated Point
Fan Speed
Static Pressure
HSP
LSP (Std. Factory Setting)
HSP: High Static Pressure
LSP: Low Static Pressure
3.1.5 Static Pressure Setting
RPI units have been provided by two Static Pressure levels regulation depending on the installation requirements:
High Static Pressure and Low Static Pressure (Std. Factory Setting) connectors are available into the Electrical Box.
Setting of Static Pressure shall be made by changing the Fan Unit connector.
5
PMML0229A rev.5 - 12/2018
Air Filter
RPI-8.0FSN3E(-f)
*
Air Flow (m
3
/min)
Hi
Med
Low
v1
v1
v3
v2
v2
v4
Remove the stay support (4 screws) from the
unit and pull down the Air Filter.
RPI-10.0FSN3E(-f)
*
Air Flow (m
3
?
N O T E
When design a duct, check to ensure that the Air volume is within
working range as indicate "Fan Performance Curve".
If the Air volume is set outside working range, water-carry-over (drop
in the ceiling or into the room), noise increases, fan motor damaged
(high temperature), insufficient Cooling/Heating capacity, phenomena
can occur.
Therefore design ducts and select the correct fan speed in order to
keep the unit running in the accepted working range.
/min)
Table des Matières
loading

Ce manuel est également adapté pour:

Rpi-10.0-fsn3e serie

Table des Matières